Page 32 - Puret Sound Energy Hand Book 1218
P. 32
Chapter 2
Figure 11 401−800 A service entrance equipment, home built on permanent foundation
SINGLE-PHASE INSTALLATION
6
2
5 4
3
6' MAX 9
5' PREFERRED 12
4' MIN
8 NO CONDUIT
IN THIS AREA
15" MIN
7
2' MIN
* 12 14
LOAD
10
1
15 16
2'-3' 1 LINE 9
NOTE: Total distance of raceway within the building to the customer’s overcurrent
protection shall not exceed 15 ft (WAC 296-46B-230.070).
* Optional grounding electrode(s) for structures without permanent foundation.
** Schedule 40 PVC or rigid-steel conduit may not be allowed on flush-mount
installations. Check with local jurisdictional codes before installation.
Items owned and installed by customer Items owned and installed by PSE
Conduit (Sch 40 or Sch 80 PVC or steel or EMT), Service conductors
4 1" single-phase, 1-1/4" three-phase 1 (residential only)
5 Insulating busing 2 Meter
6 Six terminal meter base/socket with test switch space Current transformer with meter
3 circuit wiring
7 Rigid steel conduit, Sch 40 or Sch 80 PVC **
8 Insulating bushing PSE owned but customer
purchased and installed
Current transformer enclosure (outside or in electric
9 Conduit (required in
room) 15 residential plats)
10 45˚ or 90˚ bend - rigid steel, Sch 40 or Sch 80 PVC 16 Bell end
Line and load side connectors for service conductors
11 (2-bolt lugs)
Ground electrode and wire in accordance with
12
NEC/WAC
13 Current transformer mounting bracket
14 Bell end
Electric Service Handbook 2017 — Single-Family Residential Projects 23