Figure 13 Remote metering for underground residential services on meter post
METER POST Items owned and installed by customer
1 1 6" x 6" x 8' min fully pressure-treated post,
mason block, or concrete
9 2 Service entrance equipment
2 3 Service conduit as specified in Table 7
6' MAX 4 Ground wire, in accordance with NEC/WAC
3' MIN
CONDUIT TO BE 5 Ground rod(s), in accordance with NEC/WAC
3 RIGIDLY FASTENED
TO SUPPORT 6 Service conductor to building/residence
24" MIN 7
4 Elbow, 45˚ or 90˚ bend, 24" min radius
8 Bell end
10 Items owned and installed by PSE
12 24" MIN 8
5 9 Meter
36" MIN
LINE 10 PSE service line
7 LOAD
11 2'-3' 6 PSE owned but customer provided and installed
11 Conduit (required in residential plats)
CUSTOMER’S CONDUCTOR
TO MOBILE HOME. INSTALL 12 Bell end
ACCORDING TO NEC.
Figure 14 Remote metering for underground residential services on meter pad
Items owned and installed by customer
METER PAD
1 Galvanized steel pipe
2 C-channel (unistrut) cross bracing
11 3 Service entrance equipment
2 4 Service conduit as specified in Table 7
3
6' MAX 1 5 Ground wire, in accordance with NEC/WAC
3' MIN 6 Ground rod(s), in accordance with NEC/WAC
4 7 Service conductor to building/residence
24" MIN 8 8 36" x 36" x 3" min concrete stabilizer pad
5
9 Elbow, 45˚ or 90˚ bend, 24" min radius
12 10 Bell end
24" MIN
14 10 Items owned and installed by PSE
6
LINE 11 Meter
13 2'-3' 9 LOAD 12 PSE service line
7 PSE owned but customer provided and installed
CUSTOMER’S CONDUCTOR
TO MOBILE HOME. INSTALL 13 Conduit (required in residential plats)
ACCORDING TO NEC.
14 Bell end
Electric Service Handbook 2017 — Single-Family Residential Projects 26