Page 35 - Puret Sound Energy Hand Book 1218
P. 35

Chapter 2


              Figure 13           Remote metering for underground residential services on meter post


                                METER POST                      Items owned and installed by customer

                                          1                      1  6" x 6" x 8' min fully pressure-treated post,
                                                                    mason block, or concrete
                                          9                      2  Service entrance equipment
                                          2                      3  Service conduit as specified in Table 7
                     6' MAX                                      4  Ground wire, in accordance with NEC/WAC
                     3' MIN
                                           CONDUIT TO BE         5  Ground rod(s), in accordance with NEC/WAC
                                         3 RIGIDLY FASTENED
                                           TO SUPPORT            6  Service conductor to building/residence
                         24" MIN                                 7
                                         4                          Elbow, 45˚ or 90˚ bend, 24" min radius
                                                                 8  Bell end
                       10                                       Items owned and installed by PSE
                   12    24" MIN  8
                                                        5        9  Meter
              36" MIN
                             LINE                               10  PSE service line
                                    7          LOAD
                   11    2'-3'              6                   PSE owned but customer provided and installed
                                                                11  Conduit (required in residential plats)
                                        CUSTOMER’S CONDUCTOR
                                        TO MOBILE HOME. INSTALL   12  Bell end
                                        ACCORDING TO NEC.




               Figure 14          Remote metering for underground residential services on meter pad


                                                                Items owned and installed by customer
                               METER PAD
                                                                 1  Galvanized steel pipe
                                                                 2  C-channel (unistrut) cross bracing
                                         11                      3  Service entrance equipment
                                            2                    4  Service conduit as specified in Table 7
                                         3
                   6' MAX                  1                     5  Ground wire, in accordance with NEC/WAC
                   3' MIN                                        6  Ground rod(s), in accordance with NEC/WAC
                                        4                        7  Service conductor to building/residence
                        24" MIN            8                     8  36" x 36" x 3" min concrete stabilizer pad
                                              5
                                                                 9  Elbow, 45˚ or 90˚ bend, 24" min radius
                     12                                         10  Bell end
                        24" MIN
                  14         10                                 Items owned and installed by PSE
                                                       6
                            LINE                                11  Meter
                 13     2'-3'      9         LOAD               12  PSE service line
                                           7                    PSE owned but customer provided and installed
                                       CUSTOMER’S CONDUCTOR
                                       TO MOBILE HOME. INSTALL   13  Conduit (required in residential plats)
                                       ACCORDING TO NEC.
                                                                14  Bell end









               Electric Service Handbook 2017 — Single-Family Residential Projects                          26
   30   31   32   33   34   35   36   37   38   39   40