Chapter 2
Permanent underground service for manufactured homes, 0−200 A
Service If you are installing an underground service to your manufactured home, your service
equipment equipment can be installed one of two ways:
installation • On a customer-owned pedestal or meter post (see Figure 12).
• On the manufactured home, if both of the following conditions are met:
» The manufacturer installed the service equipment at the time your home
was built.
» The service equipment meets the meter base/socket requirements listed
below.
Meter base/ Meter base/sockets installed on manufactured homes must:
socket • Be located on an outside wall of your home.
requirements
• Be located on the front one-third of your home closest to normal public access.
Refer to Meter Locations and Clearances on Page 2 of the Electric Underground
Service Installation Requirements handout for more information.
• Be between 4 and 6 feet above finished grade.
• Meet PSE’s service entrance conduit size requirements.
• Not be in a walkway or breezeway.
• Not be in an area that is subject to being fenced.
NOTE: Meter bases/sockets not installed on the manufactured home must meet the
requirements of NEC 550.32(B).
Electric Service Handbook 2017 — Single-Family Residential Projects 24