Chapter 2
400 A and larger Remote meter installations that require current transformers shall be mounted on
panels permanent support structures that are made of galvanized steel pipe with unistrut
cross-braces, concrete, or masonry blocks. Support structures made of wood
(treated or not) are unacceptable.
The customer shall provide a 3-foot x 3-foot x 3-inch-thick concrete pad surrounding
the meter or holes 2 feet deep that are filled with concrete to anchor the structure.
Meter bases/sockets shall be permanently labeled to indicate the address they
serve. PSE requires engraved phenolic nameplates or adhesive die-cut labels at least
1-inch high. Service will not be established until marking is complete.
NOTE: Felt-tip pens and label maker tape are not considered permanent marking.
Other requirements specified in this handbook for meter bases/sockets and current
transformer (CT) enclosures apply.
Remote services Remote services 800 A or greater require EUSERC outdoor switchgear. Ask your
greater than CCS Representative for more information.
800 A
Meter post Remote metering must be:
and pedestal • Accessible for reading and maintenance during normal business hours.
locations
• Not be in a walkway or breezeway.
• Not be in an area that is subject to being fenced or enclosed.
• Safe parking must be located within 50 feet of the meter.
NOTE: When installed close to PSE’s transformer, all metering equipment must be a
minimum of 3 feet from the transformer and not installed in front of the transformer.
Electric Service Handbook 2017 — Single-Family Residential Projects 27