Page 66 - B8773-AEW-XX-XX-PP-A-0001_[P1]_Contractors Manual
P. 66
4.2.5 Small Power • Install electrical supplies to ceiling mounted
cassette air conditioning system, signs,
13 amp switched socket outlets, connection local extract fans (with/without overrun
units and isolators shall be supplied and installed timers), dedicated outlets for systems etc. as
in accordance with the requirements of the necessary.
project.
• Make final connection to all items of
• All general use 13A sockets shall be white equipment unless specified otherwise.
moulded plastic outlets to BS 1363.
• Supplies to fascia signs shall be terminated
• All sockets serving computer and telephone with 1.5m length of flexible sheathed cable
equipment shall be wired on dedicated at the centre of each sign location, and
circuits with a separate clean earth fed via a time clock. The time clock shall be
connected to the clean earth bar. located in the electrical cupboard in such
a position that it can be easily seen and
• ‘Clean’ socket outlets shall normally have adjusted and instructions must be left with it.
completely red coloured faceplates, as
MEM 3190 and 3195 or similar. EXCEPT, that • The fascia sign supply MUST be clearly
those inside the monitor shrouds on the identified, and if necessary a draw wire
makeline wall ( only) must be BLACK. should left through the fascia for the sign
contractors to pull their cable through later.
• The 2no. 13A S/S/O for the Cooktek units It is NOT acceptable to simply provide a
MUST be wired on their own ring, back to fused spur internally and leave it to the sign
the MCB. Under no circumstances may they contractors to find a route to it from outside.
share another ring of any kind.
• A 20A switched fused spur, backed up by a
• Supply and install suitably sized single phase Type C MCB (Motor Rated), shall be installed
supplies, complete with separate individual to serve the cold room.
control switches located in a convenient
position near the oven, to serve extract and 4.2.6 Induction Loop
fresh air supply fans. Wire from the switches
to a local isolator adjacent to each fan and Induction Loops to assist the hard of hearing
the final connection to the fan itself. must be installed in all new stores and all re-fits
from the beginning of 2012. This will normally be
(NOTE: Power supplies to PS 200/PS540/PS640WOW ovens fitted to the Disabled section of the counter and
may be fitted by the site electrician as part of
will be standard 13A S/S/O. However, supplies to both PS his installation. The unit fitted should comply with
EN60118-4 (formerly BS6083) and BS7594:1993. A
555 series and PS 360 series ovens will require a 20A rated suitable unit is SigNET ML1/K ( Details in approved
suppliers section).
socket for each oven (Reyrolle type) and in this case,
both socket and plug should be supplied by the electrical
contractor. Plugs to be wired to ovens, by others.)
• The supply to each oven socket shall be
independent so that in the event that one
circuit breaker trips, power is not lost to both
ovens at the same time.
4.2.5 - 4.2.6 Small Power and Induction Loop 3 February 2016