4.1.3 Emergency Lighting

- Whilst a lighting layout is shown on the project
drawings, it is the express responsibility of the
Principal Contractor to ensure that emergency
lighting design is undertaken by a competent
electrical contractor.

•	 The emergency lighting must be
    provided by adding emergency packs in
    appropriate positions to the lights already
    designed into the scheme plus the design of
    MOE exit lighting.

•	 The emergency lights will require specific
    coordination when placing the lighting
    order. The electrical design must also include
    assistance alarms in wheelchair accessible
    WC’s.

•	 Flush mounting LED emergency light fittings
    are available from Microlights and should
    always be used in the Bake & Serve and
    Customer area’s

•	 Drop bulkhead style emergency lighting is
    not acceptable. All fittings to be flush.

•	 Supply and install emergency light fittings
    using concealed cabling and wired such
    that they operate in the event of local circuit
    failure.

•	 Integral emergency light packs can be
    sourced for the ambient light fittings which
    must be used throughout the store. Surface
    mounted units are not acceptable.

•	 Internally illuminated fire exit signs shall be
    supplied and installed as required.

•	 Emergency lighting test key switches shall be
    positioned adjacent to the lighting switches
    to simulate local circuit failure.

•	 Emergency lighting to be in accordance
    with BS5266, ICEL 1003 and CIBSE TM12.