    appropriateness of additional protective equipment. The result
    of  the  HAZOP  analysis  is a  technological  hazard  table  with
    ranking  by  consequences.  Next,  the  distribution of  security
    functions  by  layers  of  protection.  First  of  all,  the  possibility
    of using mechanical protections is considered such as safety
    valves, explosive diaphragms. Where this is not possible, you
    need implement instrument protection circuits.
            The determination of SIL safety integrity levels for Safety
    Instrumented  Function  (SIF)  instrument  protection circuits
    can be performed using one of the methods, for example, a
    risk matrix or analysis of LOPA (Layers of protection analysis)
    protection layers, a risk graph, etc. It should be noted that the
    level SIL is defined for the protection circuit from the sensor to
    the actuator. After determining the SIL levels, it is possible to distribute the protection functions
    according to their execution: implement the SIL0 level with a risk reduction coefficient of less
    than 10 using DCS; implement SIL1 levels and higher using EAP system. At the output of the
    stage, the Safety Requirment Specification (SRS) should appear. This is the technical task for
    the  creation  of  a  EAP  system.  The  specification  defines  blocking  circuits:  sensor-controller-
    executive device; requirements for them according to the SIL level, requirements for testing
    intervals, requirements for architecture, requirements of orders of Rostekhnadzor, etc.




























    Fig. 3.  An example of a protection circuit, where XooN is the voting scheme X of N inputs, blocking (implemented in the
    controller); YooZ - voting scheme Y from Z outputs, ensuring blocking (determined by the installation of the executive
    devices in the "field"); ED - executive device (shut-off valve, pump, etc.).



            Implementation phase                                          Operation phase
    Based on the SRS specification, instrumentation,                      Since any system degrades over time
    controller,  actuators  are  selected.  By  calculation  both in terms  of  reliability  and  in terms
    it  is  confirmed  that  the  designed  protection  of  security,  the  enterprise  should  have
    circuits  according  to  the  SIL  level  correspond  plans for testing circuit elements. They are
    to  the  required  values  from  the  specification.  tested  at  the  frequency  specified  in  the
    The  development  of  documentation  includes:  a  SRS  specification.  Test  results  should  be
    "field"  project,  a  top-level  project,  development  documented. Periodically, it is necessary to
    of  working documentation,  system  assembly,  conduct an assessment of functional safety
    acceptance tests, commissioning, complex tests.  with  the  participation  of  technologists,
    Validation  is  carried  out  this  is  the  confirmation  electricians, specialists of the instrumentation
    that the embedded algorithms and implementation  and control systems. The person responsible
    fully comply with the original requirements of the  for  maintaining  the  functional  safety  life
    SRS specification.                                             cycle must be identified. All people involved
                                                                   in the life cycle stages of a EAP system must
                                                                   be trained.