Page 371 - Installation Training Binder FIT1-3
P. 371

Step 4a

                   Battery Cabinet Installation

                          Always check for rebar or underground obstructions before drilling!

                          Assemble the cabinet according to the battery cabinet or UPS manufacturer
                          instructions.  Carefully place the cabinet onto the liner (Figure 3).  Be very
                          careful not to tear the liner by shifting the cabinet.  Be sure to place the
                          included acid-resistant support plates under feet or rollers to help
                          prevent any possible tearing of the liner.  Center the cabinet on the
                          inside of the liner. Check to ensure that distances from the wall and aisle
                          widths comply with local codes.  The liner should extend beyond the cabinet
                          evenly on all sides.



                                                                                Battery Cabinets



















                                      Figure 3



                          Mark the locations of the holes to be drilled for the battery cabinet.  Drill
                          holes for battery cabinet anchor bolts.  Clean holes and remove debris. Coat
                          each floor anchor bolt with acid-resistant sealant before placement.  Insert
                          anchor bolt through washer.  (Figure 4)  Run a bead of acid-resistant sealant
                          around cabinet footprint, anchor bolts and any open welds on cabinet that
                          would allow liquid to seep under the rack footprint.  Lay 1/8” Masonite sheet
                          over the liner when installing batteries to protect liner from equipment and
                          lifts.  Set the batteries in the cabinet. Remove Masonite and duct tape.






                                                              Figure 4




                   EnviroGuard  800-206-9884     Fax  909-624-1772               www.EnviroGuard.com

                   03/01/2017 Rev. G            Hawk System Setup Instructions                          8