"Oil-Less” Medical Air Medical Systems
3.0 System Operation (continued)
3.2 Initial Start-up (continued)
CAUTION: Only one dryer/filter/regulator group should be on line at a time.
The dryer should purge until the dew point monitor reading is below minus 12°C. When dew point is below
minus 12°C, both pressure gauges of the on-line dryer will read the same as the panel pressure gauge.
Observe the system for normal operation.
3.3 Normal Start-up
Hospital shutoff valve - CLOSED.
Isolation (shutoff) valves - OPEN.
Receiver bypass valve - CLOSED.
One air dryer off line with valves CLOSED; the other air dryer on-line with the valves OPEN.
Main electrical power - ON.
Disconnect switches - ON.
H-O-A switches - AUTO (starting all compressor units).
Pressure gauge increasing to 100 psi (689 kPa).
Check that each compressor shuts down as it reaches its off-limit pressure.
Check that the mainline regulator is set for the desired output pressure and adjust if necessary.
Slowly OPEN the hospital shutoff valve.
Note: Opening the hospital valve may cause a pressure demand that brings the lag compressors back on-line.
This is a normal sequence.
Note: The medical air system is now on-line and in the Normal Operating Mode (lead/lag operation).
To verify dryer operation, refer to Appendix A for desiccant dryers.
3-5