"Oil-Less” Medical Air                                                              Medical Systems


               3.0 System Operation (continued)

               3.2 Initial Start-up (continued)

               CAUTION: Only one dryer/filter/regulator group should be on line at a time.

               The dryer should purge until the dew point monitor reading is below minus 12°C. When dew point is below
               minus 12°C, both pressure gauges of the on-line dryer will read the same as the panel pressure gauge.

               Observe the system for normal operation.


               3.3 Normal Start-up

               Hospital shutoff valve - CLOSED.

               Isolation (shutoff) valves - OPEN.

               Receiver bypass valve - CLOSED.

               One air dryer off line with valves CLOSED; the other air dryer on-line with the valves OPEN.

               Main electrical power - ON.

               Disconnect switches - ON.

               H-O-A switches - AUTO (starting all compressor units).

               Pressure gauge increasing to 100 psi (689 kPa).

               Check that each compressor shuts down as it reaches its off-limit pressure.

               Check that the mainline regulator is set for the desired output pressure and adjust if necessary.

               Slowly OPEN the hospital shutoff valve.

               Note:  Opening the hospital valve may cause a pressure demand that brings the lag compressors back on-line.
               This is a normal sequence.

               Note:  The medical air system is now on-line and in the Normal Operating Mode (lead/lag operation).

               To verify dryer operation, refer to Appendix A for desiccant dryers.