Medical Lubricated Vacuum


            Appendix A:  TotalAlert Embedded Control System



            A.3.7   3.5” Service Screen                          A.3.8   3.5” Alarms Screen




























            Figure A.20 3.5” Service Screen                      Figure A.21 3.5” Alarms Screen

            The service screen (Figure A.20) allows access       The alarms screen (Figure A.21) shows all of the
            to the unit “jog” feature, diagnostic screen and     unit alarm information.  An alarm is classifi ed as
            version screen:                                      an event of signifi cance that does not shut the
                                                                 unit down.  These alarms are latched and are not
            •  Rotation – Allows the unit to run for a short     cleared until a user presses the reset button on
               period to check rotation.  When pressed, the      the alarms screen.  This reset button will reset all
               unit will either begin the “jog” sequence or      alarms for that given unit.
               show a screen instructing you to place the
               unit in “OFF” mode fi rst (the unit must be        •  Green alarm condition indicates a normal
               in “OFF” mode before it can check rotation).         status for that condition.
               When  “jog” mode is started, the unit will fi rst
               delay for 5 seconds to allow the user to get in   •  Red alarm condition indicates an abnormal
               position to check the rotation, then run the         status for that condition.
               unit for a brief period.

            •  Diagnostic – Depicts the I/O status of the
               connecting unit controller board.  For example,
               the digital inputs (X1-X4 as 0 or 1), the analog
               readings (T1-T3 and I1 with A/D values), the
               24VDC powered digital outputs (Z1-Z5  as 0 or
               1) and the dry contacts (Y1-Y3 as 0 or 1).
            •  Version – Displays the RS485 communication
               version, the fi rmware versions for the 3.5
               display board and the connecting controller
               board.
            •  Testing – Allows for test mode of all shutdown
               events.  See Section A.5 for more information.