Appendix A: TotalAlert Embedded Control System
After a service activity is performed, to reset the A.7.2 Set Up: Physical Connection
schedule, do the following:
WARNING:
• Select the service activity on the touchscreen
(Figure A.25). ONLY CONNECT THE CUSTOMER
NETWORK TO THE CUSTOMER
• Press the Reset button. ETHERNET CONNECTION AS SHOWN
IN FIGURE A.26.
• Enter the password (as explained in Section
A.4). DO NOT UNPLUG EXISTING ETHERNET
CABLES USED FOR THE INTERNAL
A.7 Remote Monitoring CONNECTIONS. DO NOT ATTEMPT
TO REMOVE ETHERNET SECURITY
CAUTION: The information systems personnel PROTECTORS TO USE FOR CUSTOMER
should be notifi ed before changing any of the ETHERNET CONNECTION.
network settings. Changing the settings could
keep the equipment from working properly. IF THE CUSTOMER ETHERNET IS
PLACED IN AN INTERNAL ETHERNET
A.7.1 Set Up: Equipment Required CONNECTION, THE INTERNAL
ETHERNET FUNCTIONALITY WILL NOT
• PC with an Ethernet connection PERFORM AS DESIGNED.
• PC with a web browser, such as Microsoft
Internet Explorer
• Cat5 or better Ethernet cable
Customer Ethernet Connection
on PCB3 Master
Figure A.26 Connecting the cable
1. Using a Cat5 Ethernet cable, connect the
medical vacuum system to an Ethernet switch
or hub. Connect the cable to the Customer
Ethernet Connection (Figure A.26) on PCB3
Master board.
2. Verify the green LINK LED on the printed circuit
board illuminates.