Page 531 - Med Plaza and Cancer Center
P. 531

Introduction



             Alarm Configuration                               The required alarm panel configuration may be
                                                               specified within the part number scheme as
                                                               described below:
             An alarm panel may consist of any
             combination of digital display modules, multi-
                                                               Part Number Scheme:
             signal modules, or blank modules.
                                                                                          Position within alarm
             If alarm panel is configured with digital display          1 2 3 4 5 6 7 8   panel (Figures 1 and 2)
             modules, pressure/vacuum sensors will be
             included for connection to pressure/vacuum        6-M2 ? - ? ? ? ? ? ? ? ?
             pipeline (except for 6-M2N).
             Sensors may be located inside alarm panel
             rough-in box (local sensors) or outside alarm
             panel rough-in box (remote sensors).               L = Local Sensors       Designates type of
                                                                R = Remote Sensors      alarm panel component
             Local sensors must be connected to                 N = No Sensors          from chart below
             pressure/vacuum pipelines via copper tubing            (Slave Applications)
             (Figure 3).  Remote sensor may be mounted
                                                                    O   OXYGEN
             near pressure/vacuum pipeline and then wired
                                                                    D   OXYGEN - 100 PSI
             to alarm panel (Figure 4).                             X   NITROUS OXIDE
                                                                    A   MEDICAL AIR
                                                                    F   MEDICAL AIR - 100 PSI
                                                                    5   AIR (ISO)
                                                                    7   LABORATORY AIR
                                      Copper tubes connect to                                         MODULES
                                      pressure/vacuum               2   O2-CO2
                                      pipelines                     4   O2-He
                                                                    C   CARBON DIOXIDE
                                                                    G   CARBON DIOXIDE - 100 PSI
                                                                    1   CO2-O2                        DISPLAY
                                                                    3   He-O2
                                                                    H   HELIUM
                                                                    V   VACUUM                        DIGITAL
                                                                    6   VACUUM (ISO)
                                         Sensor modules are         8   LABORATORY VAC
                                         mounted inside the         W   WAGD
                                         alarm panel box            N   NITROGEN
                                                                    9   INSTRUMENT AIR
                         Figure 3: Local Sensors                    J   ARGON
                                                                    M   MULTI-SIGNAL MODULE
                                                                    R   MULTI-SIGNAL MODULE W/ RELAYS
                  Copper tubes connect to                           B   BLANK
                  pressure/vacuum
                  pipelines
                                                               NOTE:
                                                               When an alarm panel is ordered with either local
                                                               or remote sensors, ALL sensors will either be
                                                               local or remote.  Alarm panels with a combination
                                                               of local and remote sensors are not available.

                                   Sensors have separate       NOTE:
                                   mounting boxes for mounting  Alarm panel components in table above are listed
                                   near pressure/vacuum        in order of criticality.  Unless otherwise specified,
                                   pipeline and then must be   the most critical component will fill position one,
                                   wired to alarm panel
                                                               the next less critical component will fill position
                       Figure 4: Remote Sensors                two, etc. etc.



         6
              Part No. 6-847684-00 Rev. E00