Wiring Schematic 5: Multi-Signal Module Relays (Optional)





                                                               NOTE:
                                                               Field wiring cable shields must be grounded at
                       Dry normally-closed
                                                               only one end, inside alarm panel back box.  Refer
                       contacts at source
                                                               to page 31 for details.
                       equipment or line
                       pressure switches
                                   COM    +
                         SIGNAL 1
                                   COM    +
                         SIGNAL 2

                                   COM    +
                         SIGNAL 3
                                   COM    +
                         SIGNAL 4

                                   COM    +
                         SIGNAL 5




                                                                        ribbon to
                              Multi-Signal Module                       adjacent
                                                                        module

                                                                                        SIGNAL 1 - pins 1 & 2

                                                                                        SIGNAL 2 - pins 3 & 4
                                                                                        SIGNAL 3 - pins 5 & 6

                                                                                        SIGNAL 4 - pins 7 & 8

                                                                                        SIGNAL 5 - pins 9 & 10

                                                                                  Dry normally-closed output
                                                                                        relay contacts
             NOTE:
             Output relay contacts are dry normally closed type.  Contacts open
             upon designated alarm activation.  Contacts remain open until
             alarm condition is corrected.  Alarm mute DOES NOT affect relay
             condition.  Relay contact  ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC.























         18
              Part No. 6-847684-00 Rev. E00