Typical Master/Area Alarm Wiring Examples
MASTER ALARM PANEL #1
pin 6 (-) pin 5 (+)
Oxygen
Sensor
Module
Connected to main MAIN LINE
oxygen pipeline
Digital Display Module
pin 2 (com) pin 1 (+)
O2 Secondary
Supply
Com
Multi-Signal Module
Normally-closed contacts at
high-pressure oxygen manifold
pin 2 (com) pin 1 (+)
O2 Secondary
Supply
NOTE:
Switch contacts must be dry,
normally-closed type. Alarm Multi-Signal Module
activates when contacts open.
pin 6 (-) pin 5 (+)
Oxygen
Sensor
Module
MAIN LINE
Connected to main
oxygen pipeline
Digital Display Module
MASTER ALARM PANEL #2
Example 1: Two master alarm panels with digital displays -
high-pressure manifold/no reserve (oxygen shown).