Page 669 - Med Plaza and Cancer Center
P. 669

PROPRIETARY AND CONFIDENTIAL DRAFT 28/Feb/03

                   Configuring and Browsing the Master Alarm by Using the Web Pages
                   Chapter 1: Introduction


                   Configuring and Browsing the Master Alarm by Using the Web
                   Pages


                                 To use the Master Alarm’s built-in Web Pages; you either need to have the
                                 Master Alarm connected to the facility’s Ethernet, or have it connected to a
                                 serial port on your computer (see “Setting up the Internet Interface” on page
                                 6-11).

                                 1. Before using the Web pages, set up the alarm’s Internet interface.



                                 CAUTION:
                                 Have the facility’s Information Systems personnel set up the Internet
                                 interface. If the set up is done improperly, equipment may not perform
                                 properly.

                                 2. Find the Master Alarm’s name.

                                     a. Open the Master Alarm’s Front Panel.

                                     b. Look on the label on the back of the Master Alarm Module.

                                 The label says Serial Number://Master#####, where “#####” is the unique
                                 serial number for that Master Alarm. The word Master plus its serial number is
                                 the factory-programmed name for the Master Alarm.


                                 3. Another way to find the Master Alarm’s name is as follows:
                                     a. Use a 5/32" hex wrench to open the front panel of the Master Alarm.
                                     b. Turn the power switch to the OFF position.

                                     c. Turn the power switch back to the ON position and watch the display.

                                     d. When the display reads Webbrowse@http://Master#####, that is the
                                         Master alarm’s name.

                                 4. Type the word Master followed by its serial number (without a space) into
                                     your browser’s address window (CM) (see figure 1-24 on page 1-73).



















                   Page 1 - 72           MedPlus TotalAlert™ Alarm Network Operation and Maintenance Manual (man291ra)