ZONE VALVE/ AREA ALARM / OUTLET PERFORMANCE/GAS CONCENTRATION AND PURITY INSPECTION DOCUMENT

           Facility   Florida Hospital Orlando                Inspector  Steve Gourley
          City/State  Orlando, Fl.                            Date       12-5-17         Page       1 of 2
          Contractor  n/a                                     Facility Contact   Darrell Huckaby

                        Triage Exam 1 Thru 8, Ultrasound and
          Area Served   Triage Assessment                     Floor/Bldg   Ground Floor Womens


           Zone Valve Location for this Area   Next to soiled holding   ZVB Manufacturer      Beacon
           FL Hosp. Tag #        O2 #000000171998, AIR #000000171996, VAC #000000171997
          Location IAW NFPA 99   Pass               Labeled      Pass     Gauges     Pass      Leak Test   Pass
           Test Gauge   O2     54   AIR   49   VAC    22
           Pressure vs.
           ZVB Gauge           50         50          22
           Valve Size       ¾”         ¾"         1 ½”
          Comments: *


         Gas/Pipeline Purity  Oxygen      Med Air       Comments
         Hydrocarbons             <1 PPM        <1 PPM
         Dew Point                   -44F            5F
         Carbon Monoxide          <1 PPM        <1 PPM
         Carbon Dioxide            0 PPM       120 PPM

         Gas Concentration        99%O2       21.8(%O2)
         Particulates                 <1             <1
         Odor/Discoloration         none           none
         Test Location            Exam 3         Exam 3

         Area Alarm Panel Location for this Area         Near nurses station
         Location IAW NFPA 99       Pass                 Labeled    Pass   Gauges     Pass     Leak Test   Pass
         Area Alarm Panel Manufacture Data         Beacon Total Alert 2 ADV# 000000222138
                     GAUGE     LOW      HIGH                        TEST
          GAS/VAC      PSI    ALARM    ALARM    VISUAL   AUDIBLE   SWITCH   SENSOR        COMMENTS        PASS/FAIL
            OXY        53       40       60       P        P         P         PS                           PASS
             AIR       49       40       60       P        P         P         PS                           PASS
            VAC        21       12       NA       P        P         P         PS                           PASS
        PS= Patient Side   SS= Source Side   NW= Not Working   CNT= Could Not Test   NA = Not Applicable    NP = Not Present


              Corporate Office ∙ 4518 Clements Rd. Lakeland Florida 33811 Phone: 863-646-7555 ∙ Fax 863-646-2999
                                 “Medical Gas Pipeline Equipment Service, Sales & Verifications”