Oil-Less Claw Medical Vacuum
Appendix A: TotalAlert Embedded Control System
feature of the TotalAlert Embedded control
system. By setting up the Electronic Notifi cation,
key personnel can receive notifi cations of all alarm/
shutdown alerts and/or all maintenance alerts
(e-mail, pager, phone text message). The device
acts as an SMTP client. An SMTP server is required
for electronic notifi cation to function.
Figure A.33 Website Setup
1. Click Website Setup to access the Website
Setup page.
2. Select a time interval from the pull-down list
of options.
3. Click the Submit button.
A.7.9 System Trend Setup
Figure A.35 Electronic Notifi cation Setup
1. Click Electronic Notifi cation Setup to access
the Electronic Notifi cation Setup page.
Figure A.34 System Trend Setup
2. Select Enable to enable the e-mail notifi cation
tool.
This System Trend Setup page (Figure A.34) is used
to confi gure the trend log for the website and to
allow the data to be cleared. The System Trend 3. Enter up to fi ve email addresses.
screen contains a maximum of 720 events for each
of the items recorded, so the actual duration of the 4. For each address, select “System” for that
person to receive all alarm/shutdown alerts.
trend log changes with the time interval selected. Select “Maintenance” for that person to
The durations available to select are 6 hours, 24 receive all maintenance alerts. An individual
hours, 2.5 days, and 10 days.
may receive both types of alerts.
1. Click System Trend Setup to access the System
Trend Setup page. 5. Enter an email address in the “From” box as
this will be the sender of the notifi cations.
2. Select a time interval from the pull-down list 6. If desired, early warning notifi cations can be
of options.
set up for maintenance items. By selecting
these time intervals, a notifi cation will be sent
3. Click the Submit button.
before the maintenance item is due, providing
A.7.10 Electronic Notifi cation Setup time for planning the service activity.
This Electronic Notifi cation Setup page (Figure 7. Click the Submit button.
A.35) is used to confi gure the Electronic Notifi cation