Page 500 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 500

767-5204

   6    MOVILINK  Interface (RS-232, RS-485)
                       ®
  498   2 interfaces (2 x M12) + 4 digital inputs/outputs (2 x M12, two inputs/outputs per connector)


                                                                                    MOVILINK ®
                                                            Module marking
                                                                                             System bus
                                                                                             output (3)
                                                               System bus
                                                                 input (3)
                                                                                     Ch2.1   MOVILINK ®  Interface 2
                                                              LED indicators
                                                                                          X  RS-232/RS-485 (2)
                                                                            Ch1.1         4
                                                       MOVILINK ®  Interface 1  X    Ch2.2   Channel marking
                                                          RS-232/RS-485 (2)                  (2 fields for
                                                                        3                    each port/channel)
                                                                            Ch1.2    2
                                                                                             Digital inputs/
                                                                                          X  outputs,
                                                                              0           2  channel 3 + 4
                                                             Digital inputs/  X              (2)
                                                                 outputs,            3
                                                             channel 1 + 2  1                Channel marking
                                                                    (2)       1              (2 fields for
                                                                                             each port
                                                                                             1 field for
                                                                                24 V         each channel)
                                                                                U  U
                                                                                 LS  A
                                                                 Supply        767-5204      Supply
                                                                input (1)                    output (1)


        Short description:                                  Included:
                                        ®
        Interface module for drive control via MOVILINK  protocol (see note). The ma-  • 1 x WMB marker, orange
        ximum number of drives per interface depends on the type of application and   • 1 x marking strip
        is described in more detail in the manual.          •2 x M12 protective cap
        Features:                                           Note
                                                                    ®
                   ®
        •2 MOVILINK  interfaces (RS-232, RS-485)            MOVILINK  is a registered trademark of SEW-EURODRIVE GmbH & Co. KG
        • 4 digital inputs/outputs, 24 VDC / 0.5 A
        • Diagnostic-capable (channel by channel/module by module)
        • Parametrizable (operating mode, baud rate, filter, inversion, substitute value
          strategy, substitute value, manual mode, online simulation and diagnostics)
        Description                  Item No.        Pack.    Technical Data
                                                     Unit
               ®
                                                                     ®
        MOVILINK  Interface (RS-232, RS-485)  767-5204  1     MOVILINK  Interface
                                                                Baud rate              9,600 Baud; 57,600 Baud
                                                                                              ®
        Accessories                  Item No.                   Protocols              MOVILINK  PDU types, 0x05 (cyclic)
                                                                                       and 0x85 (acyclic)
        Marking strips, marking pen, spacer   see pages 520 ... 521  Data bits (per channel)  8
        module and protective caps                              Parity                 Even
        IP67 cables and connectors   see pages 502 ... 517 + Section 11  Stop bits     1
                                                              Digital inputs:
        Technical Data                                          Number of inputs       4
                                                                Connection type (2)    M12 connectors, A coded, 5 poles,
        Module supply:                                                                 shielded
          Connection type (1)     M12 connectors, A coded, 4 poles;   Wire connection  2- or 3-wire
                                  Derating must be observed     Input filter           Hardware: ≤ 110 μs
          Current carrying capacity of supply                                          Software: parametrizable
          connections             max. 8 A (U LS : 4 A, U A : 4 A)  Input characteristic  Type 2, acc. to IEC 61131-2
          Supply voltage                                        Signal voltage (0)     -3 ... +5 VDC
                                  24 V DC (-25 % ... +30 %)     Signal voltage (1)
            Logic and sensor voltage U LS                                              + 11 VDC ... U A
                                  24 V DC (-25 % ...+30 %)      Input wiring           High-side switching
            Actuator voltage U A
          Supply current                                        Input voltage          24 VDC (-3 VDC < U IN  < +30 VDC); Power
                                  typ. 75mA                                            from U A  is strongly recommended, recovery
            Logic and sensor current I LS
                                  typ. 25 mA + Sensors (max. 400 mA) +
            Actuator current I A                                                       for voltages > U A
                                  Actuators 2.4 A (4 x 600 mA)  Input current (typ.)   7.3 mA
          Protection              Reverse voltage protection for U LS  + U A    Connection of 2-wire BEROs  max. 1.5 mA admissible closed current
                                  Short-circuit protection for sensor/actuator   Cable length, unshielded  ≤ 30 m
                                  supply                        Wrong connection of inputs  No effect
        MOVILINK  Interface                                   Input characteristic:
               ®
          Interfaces              2                             Input voltage          Typical input current
          Connection type (2)     M12 connectors, A coded, 5 poles,   -3 V < U IN  < 0 V  0 mA
                                  shielded                      5 V                    2.3 mA ... 2.5 mA
          Transmission channels   1 RxD / 1 TxD (half duplex)   11 V                   6.4 mA ... 6.7 mA
          Cable length            max. 15 m (RS-232);           24 V < U A  < 31.2 V   7.3 mA ... 7.5 mA
                                  max. 200 m (RS-485)