Page 500 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 500
767-5204
6 MOVILINK Interface (RS-232, RS-485)
®
498 2 interfaces (2 x M12) + 4 digital inputs/outputs (2 x M12, two inputs/outputs per connector)
MOVILINK ®
Module marking
System bus
output (3)
System bus
input (3)
Ch2.1 MOVILINK ® Interface 2
LED indicators
X RS-232/RS-485 (2)
Ch1.1 4
MOVILINK ® Interface 1 X Ch2.2 Channel marking
RS-232/RS-485 (2) (2 fields for
3 each port/channel)
Ch1.2 2
Digital inputs/
X outputs,
0 2 channel 3 + 4
Digital inputs/ X (2)
outputs, 3
channel 1 + 2 1 Channel marking
(2) 1 (2 fields for
each port
1 field for
24 V each channel)
U U
LS A
Supply 767-5204 Supply
input (1) output (1)
Short description: Included:
®
Interface module for drive control via MOVILINK protocol (see note). The ma- • 1 x WMB marker, orange
ximum number of drives per interface depends on the type of application and • 1 x marking strip
is described in more detail in the manual. •2 x M12 protective cap
Features: Note
®
®
•2 MOVILINK interfaces (RS-232, RS-485) MOVILINK is a registered trademark of SEW-EURODRIVE GmbH & Co. KG
• 4 digital inputs/outputs, 24 VDC / 0.5 A
• Diagnostic-capable (channel by channel/module by module)
• Parametrizable (operating mode, baud rate, filter, inversion, substitute value
strategy, substitute value, manual mode, online simulation and diagnostics)
Description Item No. Pack. Technical Data
Unit
®
®
MOVILINK Interface (RS-232, RS-485) 767-5204 1 MOVILINK Interface
Baud rate 9,600 Baud; 57,600 Baud
®
Accessories Item No. Protocols MOVILINK PDU types, 0x05 (cyclic)
and 0x85 (acyclic)
Marking strips, marking pen, spacer see pages 520 ... 521 Data bits (per channel) 8
module and protective caps Parity Even
IP67 cables and connectors see pages 502 ... 517 + Section 11 Stop bits 1
Digital inputs:
Technical Data Number of inputs 4
Connection type (2) M12 connectors, A coded, 5 poles,
Module supply: shielded
Connection type (1) M12 connectors, A coded, 4 poles; Wire connection 2- or 3-wire
Derating must be observed Input filter Hardware: ≤ 110 μs
Current carrying capacity of supply Software: parametrizable
connections max. 8 A (U LS : 4 A, U A : 4 A) Input characteristic Type 2, acc. to IEC 61131-2
Supply voltage Signal voltage (0) -3 ... +5 VDC
24 V DC (-25 % ... +30 %) Signal voltage (1)
Logic and sensor voltage U LS + 11 VDC ... U A
24 V DC (-25 % ...+30 %) Input wiring High-side switching
Actuator voltage U A
Supply current Input voltage 24 VDC (-3 VDC < U IN < +30 VDC); Power
typ. 75mA from U A is strongly recommended, recovery
Logic and sensor current I LS
typ. 25 mA + Sensors (max. 400 mA) +
Actuator current I A for voltages > U A
Actuators 2.4 A (4 x 600 mA) Input current (typ.) 7.3 mA
Protection Reverse voltage protection for U LS + U A Connection of 2-wire BEROs max. 1.5 mA admissible closed current
Short-circuit protection for sensor/actuator Cable length, unshielded ≤ 30 m
supply Wrong connection of inputs No effect
MOVILINK Interface Input characteristic:
®
Interfaces 2 Input voltage Typical input current
Connection type (2) M12 connectors, A coded, 5 poles, -3 V < U IN < 0 V 0 mA
shielded 5 V 2.3 mA ... 2.5 mA
Transmission channels 1 RxD / 1 TxD (half duplex) 11 V 6.4 mA ... 6.7 mA
Cable length max. 15 m (RS-232); 24 V < U A < 31.2 V 7.3 mA ... 7.5 mA
max. 200 m (RS-485)