Page 498 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 498

767-5203

   6    Serial Interface (RS-232, RS-422/-485)

  496   2 interfaces (2xM12) + 4 digital inputs/outputs (2xM12, two inputs/outputs per connector)


                                                                                     SERIAL
                                                            Module marking
                                                                                             System bus
                                                                                             output (3)
                                                               System bus
                                                                 input (3)
                                                                                     Ch2.1   Serial interface 2
                                                              LED indicators                 RS-232/
                                                                                          X
                                                                            Ch1.1         4  RS-422/485
                                                                                             (2)
                                                            Serial interface 1  X    Ch2.2
                                                                 RS-232/  3                  Channel marking
                                                              RS-422/485                     (2 fields for
                                                                    (2)     Ch1.2    2       each port/channel)
                                                                                          X  Digital inputs/
                                                                              0           2  outputs (2),
                                                             Digital inputs/  X              channel 3 + 4
                                                               outputs (2),          3       Channel marking
                                                             channel 1 + 2  1                (2 fields for
                                                                              1              each port
                                                                                             1 field for
                                                                                24 V         each channel)
                                                                                U  U         Supply
                                                                                 LS  A
                                                                 Supply        767-5203      output (1)
                                                                input (1)



        Short description:                                  Included:
        The serial interface module controls/monitors devices (e.g., barcode readers,   • 1 x WMB marker, orange
        printers, scales, laser measurement systems, operator panels, transponders)   • 1 x marking strip
        and offers in addition digital inputs/outputs.      •2 x M12 protective cap

        Characteristics:
        • 2 serial interfaces (RS-232, RS-422/-485)
        • 4 digital inputs/outputs, 24 VDC / 0.5 A
        • Diagnostic capable (per channel/per module)
        • Parametrizable (serial interface, operating mode, filter, inversion, substitute
          value strategy, manual mode, online simulation and diagnostics)


        Description                  Item No.        Pack.    Technical Data
                                                     Unit
        Serial Interface (RS-232, RS-422/-485)  767-5203  1   Digital inputs:
                                                                Number of inputs       4
        Accessories                  Item No.                   Connection type (2)    M12 connectors, A-coded, 5 poles,
                                                                                       shielded
        Marking strips, marking pen, spacer   see pages 520 ... 521  Wire connection   2- or 3-wire
        module and protective caps                              Input filter           Hardware: ≤ 110 μs
        IP67 cables and connectors   see pages 502 ... 517 + Section 11                Software: parametrizable
                                                                Input characteristic   Type 2, acc. to IEC 61131-2
        Technical Data                                          Signal voltage (0)     -3 V ... +5 V DC
                                                                Signal voltage (1)     +11 V ... U A  DC
        Module supply:                                          Input wiring           High-side switching
          Connection type (1)     M12 connectors, A coded, 4 poles;   Input voltage    24 VDC (-3 VDC < U IN  < +30 VDC);
                                  Derating must be observed                            Power from U A  is strongly recommended,
          Current carrying capacity of supply                                          recovery for voltages > U A
          connections             max. 8 A (U LS : 4 A, U A : 4 A)  Input current (typ.)  7.3 mA
          Supply voltage                                        Connection of 2-wire BEROs  max. 1.5 mA admissible closed current
                                  24 V DC (-25 % ... +30 %)     Cable length, unshielded  ≤ 30 m
            Logic and sensor voltage U LS
                                  24 V DC (-25 % ...+30 %)      Wrong connection of inputs  No effect
            Actuator voltage U A
          Supply current                                      Input characteristic:
                                  typ. 75 mA + sensors (max. 400 mA)  Input voltage    Typical input current
            Logic and sensor current I LS
                                  typ. 25 mA + actuators 2.4 A (4 x 600 mA)  -3 V < U IN  < 0 V  0 mA
            Actuator current I A
          Protection              Reverse voltage protection for U LS  + U A    5 V    2.3 mA ... 2.5 mA
                                  Short-circuit protection for sensor/actuator   11 V  6.4 mA ... 6.7 mA
                                  supply                        24 V < U A  < 31.2 V   7.3 mA ... 7.5 mA
        Serial interface:
          Interfaces              2
          Connection type (2)     M12 connectors, A-coded, 5 poles,
                                  shielded
          Transmission channels   1 RxD / 1 TxD (full/half duplex)
          Type of cable, cable length  15 m (RS-232); 1000 m (RS-422/-485)
          Baud rate               300 – 115,200 baud
          Buffer                  4 KB (In); 4 KB (Out)