Page 501 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 501

6

                                                                                                                    499


                           System bus   1: RD+/TD+                                   Block diagram
                            Input               Output  2: RD--/TD--                                        Supply
                                        3: TD--/RD--                  Digital Input/Output
                                        4: TD+/RD+                    X1 ... X2
                                        5: GND                                                               M12
                             M12 B coded  Housing: Shield
                                                                       M12                                    2
                                                                        3               Diagnostics sensor/actuator supply  4
                         MOVILINK ®  interface   RS-232  RS-485
                          X3      X4    1:  n.c.   Tx+/Y                1
                                        2:  TxD   Tx-/Z                                     Input 0 ... 3
                                        3:  n.c.   Rx+/A                                                  10 nF  10 nF
                                        4:  RxD   Rx-/B                                          Logic
                                        5:  GND   GND
                             M12 A coded                                4/2                Output 0 ...3
                                        Housing: Shield
                                       1: 24 V                             270 pF  270 pF
                       Digital inputs/outputs   3: 0 V U
                            X1 ... X2      A                            5
                      (two inputs/outputs / connector)
                                       5: n.c.                          2
                                                                        1
                                       4: In-/Output A                         270 pF 270 pF
                             M12 A coded                                4
                                       2: In-/Output B
                                       Housing: Shield                  3                            ®  Error
                            Supply                                     M12                   Input/Output  MOVILINK    F
                                                                                                  Interface
                                                                                  270 pF 270 pF  0 ... 3
                             Input              Output                                             1 + 2
                                        1: 24 V U
                                        2: 24 V U LS
                                        3: 0 V U  A
                                        4: 0 V U LS                    MOVILINK ®  Interface
                             M12 A coded    A                          X3 ... X4                          Module mount
           Technical Data                                       Technical Data
           Digital outputs:                                     System bus:                                         6
            No. of outputs          4                             Connection type (3)     M12 connectors, B coded, 5 poles,
            Connection type (2)     M12 connectors, A coded, 5 poles,                     shielded
                                    shielded                    Standards and approvals:
            Wire connection         2- or 3-wire                  Conformity marking      1
            Output voltage          ≤ U A                         r UL 508
            Output current (per channel)  0.5 A (max. 0.6 A),   Isolation:
                                    short-circuit/overload proof   Channel – Channel      no
                                    (thermal disconnection)       U LS , U A , system bus  500 V DC each
            Voltage drop against U A  at 500 mA  max. 0.2 V DC  Parameterizable functions, MOVILINK  interface
                                                                                         ®
            Output current (module)  max. 2 A                     Operating mode (per module)  Easy Modus; Mailbox Modus
            Leakage current in OFF state  typ. 5 μA               Type (per channel)      RS-232; RS-485
            Output circuit          High-side switching           Baud rate (per channel)  9,600; 57,600 baud
           Information on actuator selection:                   Parameterizable functions, digital inputs/outputs
            Delay time hardware from "0" to "1"                   Operating mode, input filter, inversion,
            (0 – 90%)               typ. 90 μs (resistive load)   substitute value strategy, manual mode,
            Delay time hardware from "1" to "0"                   online simulation and diagnostics  For details, see manual.
            (0 – 90%)               typ. 310 μs (resistive load)  I/O diagnostics:
            Rise time from "0" to "1"  typ. 60 μs (resistive load)  I/O diagnostics (per channel)  Overtemperature (DO)
            Fall time from "1" to "0"  typ. 45 μs (resistive load)  I/O diagnostics (per module)  Sensor/Actuator supply short-circuit/
            Cable length            ≤ 30 m                                                overload
            Reverse current (in case of recovery for                                      Undervoltage (U LS  + U A )
            voltages > U A )        ≤ 1 A (error: 1 channel)    Process image:
            Type of load            Inductive, resistive loads and lamps  Process data width  Interface: 10-byte In/Out data;
            Switching frequency     Inductive load approx. 20 Hz                          DIO: 1-byte In/Out data + 1-byte status
                                    Resistive load approx. 500 Hz   LED indicators:
                                    Lamp load approx. 500 Hz      SB: System bus status   LED (green/red/orange)
            Parallel connection of 2 outputs  for power boost     F: Error status         LED (red)
                                    for redundant actuation of a load  0 – 3: Signal status, inputs/outputs  LED (yellow/red)
            Type of protective circuit  External protection (e.g., recovery diodes)  Ch1.1 + Ch2.1: Transmission status  LED (yellow)
            Output resistance       < 0,4 Ω                       Ch1.2 + Ch2.2: Reception status  LED (yellow/red)
           Operating state influence on output:                   U LS  + U A : Supply status  LED (green)
            PLC CPU stop            Acc. to substitute value strategy  Indicators         Non-latching
            Fieldbus disruption     Acc. to substitute value strategy
            S-bus (system bus) disruption  0 V status
            Supply voltage under rated voltage
            tolerance               0 V status
            Interruption of supply voltage  0 V status
            Output operation        Non-latching                General Specifications
            Overload behavior       Automatic restart
                                                                Dimensions (mm) W x H x L  35.7 x 50 x 117
                                                                Weight                    260 g
   496   497   498   499   500   501   502   503   504   505   506