14     Tests and Testing Procedures per IEC/EN Standards (continued)


  588 Electrical Tests (continued)

        • Voltage Drop Test to IEC/EN 60947-7-1
        The Voltage Drop Test evaluates clamping point quality under stresses such as vibrations, temperature changes and corrosive
        influences, in order to verify that the contact point is gas-tight.
                                                          ®
                                           The CAGE CLAMP  and
                                                      ®
                       mV                  CAGE CLAMP S connections enclose
                                           and contain flexible conductors. There-
                                           fore, a variation of the voltage drop with
                                           solid and fine-stranded conductors is so
                                           small that its influence may be negligible
                                           for the practical application of the termi-
                                           nal blocks.


               A
            1 __  I
           10  Test

        Test arrangement: “Voltage Drop Test”

        Typical voltage drop variations for solid and fine-stranded conductors of 280 to 285 Series CAGE CLAMP
                                                                                             ®
        rail-mounted terminal blocks:
          Voltage drop ∆U
          per through contact in mV



          3.2





            2                                                               fine-stranded

                                                                            solid
            1


                                                              35mm²
                2.5mm²    4mm²     6mm²     10mm²    16mm²    35mm²



        Example:   Current load cycling test result for rail-mounted terminal blocks (item no. 285-195) using 95 mm² (AWG 4/0) fine-
               stranded copper conductors:
                                                                              Voltage drop variation over longer peri-
                                                                              ods under current load cycling conditions

              50                                                              is shown for WAGO rail-mounted termi-
                                                                              nal blocks.
              45
              40
          Voltage drop ∆U  per through contact in mV  35  Voltage drop measured at the trough contacts of
                    rail-mounted terminal blocks numbered 1 – 3
              30
              25
              20
              15
              10
               0
                  0  50  100  150  200  250  300  350  400  450  500  550  600  650  700  750  800  850  900  950  1000  1050

                   V1       V2      V3       (rail-mounted  terminal block numbered 1 – 3)