Page 53 - GM booklet 2019 test
P. 53
Total 107 Hotspots in 65 locations (out of 325 locations) were identified with abnormal
temperatures and taken suitable remedial action to mitigate hotspots during the
period June to Aug-2019.
PCEE/SCR has awarded group cash award in recognition of innovative work done by
the supervisors and staff of Hyderabad Division.
HQ has issued a special drive for all other divisions of the zone based on the above
initiation by HYB Division.
Quick Watering facilities to Platforms of Kacheguda Railway Station – Work under
progress:
Quick Watering arrangements to Platforms 3 & 4 of KCG Station are under progress.
Provided 3 pumps of 50HP capacity with specification 2-Pole, Rated power 37 KW,
frequency 50 Hz, Rated Voltage 415V, Rated current 60.5A, PF 0.91, Efficiency (FL) 93.7%,
Insulation Type - F.
Quick Watering arrangements to Platforms 3 & 4 of KCG Station
Optimization of Lightly loaded substations at NLGD and SLGD:
In the process of optimization of the performance of the available transformers, the loads
connected on the various transformers were studied and found some transformers are very
lightly loaded and some transformers are not loaded upto the optimum levels. The
transformer gives optimum efficiency when Iron losses are equal to Copper losses. Iron
losses of the transformer are constant irrespective of the connected load and copper losses
are directly proportional to the square of load current.
By shifting the loads of the lightly loaded transformers to the transformers where the
loads were not upto the optimum levels, Division has eliminated the constant losses (5% of
transformer capacity) of lightly loaded transformers.
Alternate Anticipated
Name Transfor Source Protection Load in kVA Anticipated Annual
of the mer Make Substatio MCCB Annual Energy Savings
SS Capacity Before After Savings in kWh
n (Rs.)
2 x 250 SSE/NLGD
LGDH ECE 200A 140 190 35040 273312
kVA Office SS
IRISE 2 x 250 Kirloskar IRISET- 2 200A 190 230 35040 273312
T kVA
2 x 250 Lekha
LOFP HPE 200A 190 240 35040 273312
kVA Bhavan
2 x 160 ECS/MLY
MLY ETE 400A 110 140 22425 174920
kVA SS
New
GLR/ 1 x 100 Colony
Ayyappa
Colon kVA -- Feeder SS 100A 60 74 14016 109325
y
46