Page 75 - Condition Monitor User Manual
P. 75

Configuring a Monitor



































                                           Figure 7-17 Sample Flux-S Configuration

                                       Note:
                                       Properly configuring the Flux measurement requires that the asset be
                                       running.

                          Press the ‘Perform Measurement’ button.  The application will connect to the Guard and
                       get a fresh set of Flux data.  Once the data is collected, the graph will update:
                          •  If the graph reports a measurement status of ‘OK’, then the attenuation setting is
                              correct.
                          •  If the graph reports a signal amplitude problem, adjust the attenuation setting and
                              then perform a new measurement.  Keep adjusting the attenuation until the graph
                              reports a measurement status of 'OK'.

                          For  Flux-R  data,  also  check  the  analysis;  if  the  leading  peaks  were  not  properly
                       identified, then there may be something wrong with the asset configuration; perhaps the
                       number of coils is not correct.