Page 77 - Condition Monitor User Manual
P. 77

Configuring a Monitor



              7.5.4.  Original GuardII Flux Alert Configuration

                          Press the ‘Flux’ button on the ribbon and then select ‘Alerts’ to configure the Flux Alert
                       thresholds.  If the Alert settings in the monitor are different from the Alert settings in the
                       database, you will be asked which Alert settings to use.  Configuring Alerts is a different
                       process for Flux-R and Flux-S.

                          To set an Alert threshold for Flux-R:
                          •  Select one or more rows in the table.

                          •  Enter the new Alert threshold in the text box.
                          •  Press ‘Set Threshold’ to set the threshold(s) for the selected coils.
                          •  Changes can be uploaded immediately by pressing ‘Save Changes’ or later using
                              the ‘Upload’ button in the ribbon (see Section 7.8).
                          •  Pressing  ‘Discard  Changes’  will  revert  the  thresholds  to  the  previously  loaded
                              values.

































                                           Figure 7-20 Sample Flux-R Alert Settings
                                       Note:
                                       Flux Alert thresholds are expressed in % difference of the peak flux
                                       density.  So, an Alert threshold of ‘3.00’ means that ‘if the flux density
                                       of this coil/pole is more than 3% smaller than the flux density of the
                                       comparison coil/pole, an Alert occurs’.