                                       Note:
                                       On  a  salient  pole  machine,  a  pole  typically  shows  some  sign  of
                                       problems  when  the  percentage  difference  of  the  flux  amplitude  is
                                       more than 1-2%.
                                       On round rotor machines, this increases to about 3% for coils with
                                       more than 10 turns per coil, and 5-10% for coils with less than 10 turns
                                       per coil.

                          To set an Alert threshold for Flux-S:

                          •  Press ‘Acquire Data’ to get a fresh set of data on the graph.  This step is optional,
                              but it does allow you to see what the current measurement results are.

                          •  Select one or more poles on the diagram.
                          •  Enter the new Alert threshold in the text box.

                          •  Changes can be uploaded immediately by pressing ‘Save Changes’ or later using
                              the ‘Upload’ button in the ribbon (see Section 7.8).

                          •  Pressing  ‘Discard  Changes’  will  revert  the  thresholds  to  the  previously  loaded
                              values.

                          •  There are some additional controls to assist with pole selection, and the graph can
                              be re-scaled to suit the data being displayed.

































                                           Figure 7-21 Sample Flux-S Alert Settings