Page 14 - GuardII+ Series 4208 Platform SM User Manual
P. 14

GuardII+ SM Card Operation



              4.1.  Online vs. Offline

                        While online, GuardII+ does not require user intervention for any basic functionality; it will
                     run  measurements,  evaluate  SM  data,  save  measurements  in  the  Archive,  and  produce
                     measurement results via Modbus.  This is the normal mode of operation.

                        While offline, GuardII+ stops collecting data.
                                     WARNING:
                                     The monitor MUST be online for normal operation.
                                     If GuardII+ is turned on, but has been offline for more than 24 hours, it will
                                    automatically go online.


              4.2.  SM Measurement Cycle

                        SM measurements are performed every 30 minutes; on the hour and at half-past the hour.
                     When performing SM measurements, the monitor will run through the following cycle:
                        •  Collect and analyze SM data
                        •  Update Operating Condition data.

                        •  Check measurement data for new Alerts; activate the Alert if necessary.
                        •  Update Modbus slave SM data.

                                     NOTE:
                                     When  a  GuardII+  includes  other  technologies  such  as  magnetic  flux
                                     monitoring or endwinding vibration monitoring, the SM measurement cycle
                                     time  will  not  be  significantly  affected  by  these  other  monitoring
                                     technologies.


              4.3.  Operating Conditions
                        Measurement results can be affected by the current Operating Conditions of the asset
                     such as voltage, active power/load, temperature, humidity, etc.  Operating Conditions help
                     when analyzing collected data.
                        There are three available sources of Operating Condition data:
                        •  Directly from a Modbus slave

                        •  From a Remote I/O Unit (optionally included with the GuardII+)
                        •  From the ambient condition sensor (optionally included with the GuardII+)

                        The following operating conditions can be measured during SM monitoring.

                      Operating Condition      Units                 Acquired Using:
                      Active Power             W, kW, MW, hp         Modbus, Remote I/O
                      Reactive Power           var, kvar, Mvar       Modbus, Remote I/O
                      Field Voltage            Vdc, kVdc             Modbus, Remote I/O
                      Field Current            Adc, kAdc             Modbus, Remote I/O