PARTICULAR ELECTRICAL SPECIFICATION
                                 Version 2014-2


               1.10.3  Lighting

                      The Electrical Contractor will call-off the quantities and types of luminaires required to
                      complete the lighting installation. The Contractor is reminded to place the order for the
                      luminaires as early as possible, as some fittings are on long delivery.

                      Crew room lighting will be as indicated on the Architects’ reflected ceiling plan.

               1.10.1  Emergency Lighting

                      The Electrical Contractor will determine the number and location of luminaires in the
                      Architects lighting layout that are to be fitted with emergency conversion packs to meet the
                      requirements of BS 5266.

                      The  Electrical Contractor will determine the appropriate quantity and location of escape
                      signs, escape signage provisions will comply with the requirements of BS 5266.


               1.10.1  Fire Alarms

                      Detection and alarms are to be provided for all areas of the store, the Electrical Contractor
                      will determine the most appropriate number and location of detectors, alarm sounders and
                      break glass units to meet the requirements of BS5839-1.


                      Detectors in the crew room and toilets spaces will be the optical smoke type. Smoke
                      detectors will be provided in all spaces.

                      Additional sounders will be provided in the crew room to maintain the minimum alarm level
                      5dB (A) above ambient.