PARTICULAR ELECTRICAL SPECIFICATION
Version 2014-2
1.10.3 Lighting
The Electrical Contractor will call-off the quantities and types of luminaires required to
complete the lighting installation. The Contractor is reminded to place the order for the
luminaires as early as possible, as some fittings are on long delivery.
Crew room lighting will be as indicated on the Architects’ reflected ceiling plan.
1.10.1 Emergency Lighting
The Electrical Contractor will determine the number and location of luminaires in the
Architects lighting layout that are to be fitted with emergency conversion packs to meet the
requirements of BS 5266.
The Electrical Contractor will determine the appropriate quantity and location of escape
signs, escape signage provisions will comply with the requirements of BS 5266.
1.10.1 Fire Alarms
Detection and alarms are to be provided for all areas of the store, the Electrical Contractor
will determine the most appropriate number and location of detectors, alarm sounders and
break glass units to meet the requirements of BS5839-1.
Detectors in the crew room and toilets spaces will be the optical smoke type. Smoke
detectors will be provided in all spaces.
Additional sounders will be provided in the crew room to maintain the minimum alarm level
5dB (A) above ambient.