PARTICULAR ELECTRICAL SPECIFICATION
                                 Version 2014-2


                      Each hand dryer will be provided with a dedicated fused connection unit mounted at high
                      level in the toilet space, the installation will be as described by the Technical Specifications
                      for Electrical Installations Generally.

               1.8.1.3  Disable Toilet Alarm

                      Where the scope of the project include the refurbishment of the disabled toilet the Electrical
                      Contractor is to supply and install a new disabled toilet alarm system as described in the
                      Technical Specifications for Electrical Installations Generally.

               1.8.2  Lighting

                      The Electrical Contractor will call-off the quantities and types of luminaires required to
                      complete the lighting installation. The Contractor is reminded to place the order for the
                      luminaires as early as possible, as some fittings are on long delivery.

                      Lobby lighting will be as indicated on the Architects’ reflected ceiling plan.

               1.8.3  Emergency Lighting


                      Emergency lighting in the lobby area will be provided using E3R fittings.

                      The Electrical Contractor will determine the number and location of luminaires that are to be
                      fitted to meet the luminance requirements of BS 5266.

                      The Electrical Contractor will use the Architects’ fire route drawing to determine the
                      appropriate quantity  and location of escape signs, escape signage provisions will comply
                      with the requirements of BS 5266.

               1.8.4  Fire Alarms

                      Detection and alarms are to be provided for all areas of the store, the Electrical Contractor
                      will determine the most appropriate number and location of detectors, alarm sounders and
                      break glass units to meet the requirements of BS5839-1.

                      Detectors in the lobby spaces will be the optical smoke type. Smoke detectors will be
                                                                             2
                      provided in all spaces with an enclosed area greater than 1m .
                      Additional sounders will be provided in the lobby area to maintain the minimum alarm level
                      5dB (A) above ambient.