PARTICULAR ELECTRICAL SPECIFICATION
                                 Version 2014-2


                      installed as indicated  in the appendices of the Technical Specifications for Electrical
                      Installations Generally.

                      The Electrical Contractor will confirm the size of the cable to suit the rating of the protection
                      device, taking account of any applicable de-rating factors.

                      Where hanging sockets are required, the outer sheath of the cable to the in-line socket will
                      be black.

               1.7.3  IT Power Distribution

               1.7.3.1  Distribution Board

                      A new 12 way SP&N IT power distribution board (IP) will be provided to allow the connection
                      of all new equipment and services, refer to the Technical Specifications for Electrical
                      Installations Generally for details.


                      The IT distribution board will be connected to the existing main distribution board where
                      possible; otherwise it will be connected to the Kitchen distribution board as described.

                      The associated MCCB or MCB will be rated at 45A.

                      The cable between the main or  Kitchen distribution board and the IT distribution pane
                                                       2
                      assembly will be installed as a 10mm  3-core LSF insulated YY multi-core cable on tray.
                      The Electrical Contractor will confirm the final size  of the cable to suit the rating of the
                      protection device, taking account of any applicable de-rating factors.

               1.7.3.2  Connections to Digital Screens

                      A BS1363 twin switched socket will be provided at the location of each item of equipment as
                      identified on the specialist installers’ drawings, or otherwise as identified by the Technical
                      Specifications for Electrical Installations Generally.

                      Sockets for digital display equipment and devices will generally be located in service voids;
                      sockets will be located so as to be readily accessible within the voids.

               1.7.3.1  Protective Devices

                      All circuits will be provided with 30mA RCBO protection without exception. Circuit overload
                      protection will be selected in accordance with the following table:


                      Circuit type                   RCBO rating
                      Radial to sockets (≤5 number)   20A
                      Ring to sockets (≥5 number)    32A
                      Data cabinet                   16A