PARTICULAR ELECTRICAL SPECIFICATION
                                 Version 2014-2


               1.7.3.1  Cabling

                                                                                 2
                      Cabling to new devices and equipment will be installed as 4.0mm  LSF insulated YY multicore
                      cables on tray. Circuits connecting to more than 5 twin sockets will be installed as a ring; all
                      others will be installed as radial.

                      The Electrical Contractor will confirm the size of the cable to suit the rating of the protection
                      device, taking account of any applicable de-rating factors.

               1.7.4  IT Installations

                      The Electrical Contractor will provide cable basket containment for the use of the digital
                      equipment installer, as described by the Technical Specifications for Electrical Installations
                      Generally.

               1.7.5  Lighting


                      The Electrical Contractor will  call-off the quantities and types of luminaires required to
                      complete the lighting installation. The Contractor is reminded to place the order for the
                      luminaires as early as possible, as some fittings are on long delivery.

               1.7.5.1  Kitchen Lighting


                      Where identified by the project scope, provide a new lighting installation in accordance with
                      the requirements of the Technical Specifications for Electrical Installations Generally.

                      Refer to the HVAC Contractor for the setting out of the ceiling grid and the location of
                      accessible tiles and grilles.

                      The Electrical Contractor will lay out the lighting distribution to avoid blocking access tiles,
                      light fittings will generally be installed across the access corridor aisles.

                      The linear kitchen lighting will generally be installed perpendicular to the aisles, excepting
                      where this will require the light fitting to be  located  over a hot cooking surface, at hot
                      surfaces the light fittings will be installed along the aisle, refer to the appendices in the
                      Technical Specifications for Electrical Installations Generally.

               1.7.6  Emergency Lighting

               1.7.6.1  Kitchen Area

                      The main lighting in the kitchen is not available with an emergency conversion. Emergency
                      lighting in the kitchen will be provided using E3R recessed fittings.


                      The Electrical Contractor will determine the appropriate number and distribution of fittings
                      to be installed in the kitchen to achieve the required luminance level.