PARTICULAR ELECTRICAL SPECIFICATION
                                 Version 2014-2


                      Sub-Main         MCCB rating             Cable type and size
                      Distribution ref                     2                   2

                      KP                   160A      70mm   5-core YY 50mm   tri-rated in
                                                                         trunking
                                                     on tray
                                                            2
                                                                               2
                      GP                   200A      120mm   5-core YY  70mm   tri-rated in
                                                                         trunking
                                                     on tray

                      The Electrical Contractor will confirm the final size of the cables to suit the rating of the sub-
                      main protection device, taking account of any applicable de-rating factors.

                      Existing equipment connected to a kitchen bus-bar is to be retained as connected, unless
                      otherwise instructed by the Project Manager.

                      Where no spare circuit ways are available at the existing main switchboard, the IT Power
                      distribution pan assemble will be connected at the final MCB of the Kitchen Distribution
                      board.

               1.7.2.2  Connections to Kitchen Equipment

                      All new equipment and equipment chases will be provided with electrical supply connections
                      from the new Kitchen Distribution.


                      Supplies to new equipment will be provided with in-line or wall mounted sockets in
                      accordance with the requirements identified on the kitchen equipment suppliers’ drawings,
                      or otherwise as indicated in the appendices of the Technical Specifications for Electrical
                      Installations Generally.

               1.7.2.3  Protective Devices


                      The MCBs  associated with the kitchen equipment supplies will generally be selected to
                      match the rating of the socket requested by the kitchen equipment supplier or otherwise as
                      indicated in the appendices of the Technical Specifications for Electrical Installations
                      Generally.

                      All plug and socket supplies will be fitted with 30mA RCD protection, without exception.

                      The Electrical Contractor will check the size and rating of cables installed connected to the
                      plugs by the kitchen equipment supplier and adjust the rating of the associated circuit
                      breakers in the Kitchen Panel to maintain the safe operation of the distribution. The
                      Electrical Contractor will notify the Project Manager of any discrepancies identified.

                      Modifications to breaker ratings are to be identified and noted in the record documentation.

               1.7.2.4  Cabling

                      Cabling to new devices and equipment will be installed as LSF insulated multicore cables on
                      tray, circuits will be radial unless otherwise agreed with the Project Manager. Cabling will be