GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



                         Trunking lid fittings shall be provided at a maximum spacing of 1m. Short lengths of
                         trunking lid shall have a minimum of two pairs of fixing. Only purpose made
                         manufacturers’ fixings shall be allowed.

               2.9.1.2  Installation

                         Trunking shall be installed neatly running truly vertical, horizontal or parallel with the
                         features of the building and shall not be installed closer than 150mm to any other non-
                         electrical services. Main trunking runs are detailed on the drawings.

                         Trunking shall only be installed in areas, where it will be fully accessible.

                         All trunking shall be properly supported as detailed in  IET  Regulation and as the
                         manufacturers’ recommendations.

                         The majority of trunking is fixed at high level to the soffit. The trunking shall be supported
                         at a minimum of 3m centres. Supports shall be by galvanised steel channels via M6
                         channel nut, bolt and shakeproof washer. Trapeze type brackets shall be supported by M6
                         galvanised screwed rod supported from the roof purlins by purpose made clips.
                         Where trunking is fixed to parts of the structure which is liable to movement, the trunking
                         shall incorporate a flexible coupling.

                         All fixing screws within the trunking shall have round heads, to prevent abrasion of cutting
                         of cables, and shall be of adequate size. The trunking shall be free of any sharp edges.

                         Where a trunking passes through a wall or floor, a short section of lid shall be fitted to the
                         trunking, which shall protrude a maximum of 50mm. either side of the wall or floor. Prior
                         to trunking being installed through a load bearing wall or floor the approval of the
                         Structural Engineer will be required.

               2.9.2  Plastic Trunking

               2.9.2.1  Fitting

                         Plastic trunking and accessories shall comply with BS 4678: Part 4, and BS 4607
                         respectively.

                         Plastic cable trunking shall be smooth inside and outside, free from imperfection and
                         produced by an approved manufacturer.

                         Plastic cable trunking shall be of the high impact resisting heavy gauge type complete with
                         well fitting lids.

                         Dado trunking will be as manufactured by MK Electric, their catalogue reference Prestige
                         3D dado, or equal and approved.






                                                      McDonalds Restaurants Ltd

                                                                35