Page 53 - RotF - Electrical Specification_Neat
P. 53

GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2






               2.8   CABLE DISTRIBUTION

               2.8.1  Type of Wiring System

                         The cables and wiring systems shall be the types as detailed below: -

                          Use                   Wiring System

                          Main                  LSF single core fixed in galvanised steel trunking
                                                XLPE insulated copper cables with LSF sheath, fixed to galvanised
                                                channel steel support by nylon cleats
                          Sub-Main              LSF insulated copper cables (6491B) enclosed in galvanised steel
                                                trunking and XLPE/SWA/LSF cables
                          Kitchen Area          PVC/SWA/LSF cables fixed to cable tray at the fabric of the building
                                                and LSF  insulated cables enclosed in steel trunking and plastic
                                                conduit and YY PVC/LSF cables fixed to cable tray
                          General Lighting      LSF  insulated  copper Small Power cables (6491B) enclosed in
                                                galvanised steel trunking and heavy duty plastic  conduit and
                                                Telemecanique lighting bus bar system c/w tap offs, feeder units
                                                and Rendar distribution units (5way 10A)
                          Restaurant Power      LSF  insulated  copper cables lighting & (6491B) enclosed in
                                                galvanised steel cable trunking and heavy duty plastic conduit  and
                                                YY PVC/LSF cables fixed to cable tray
                          HVAC        Plant     L andSF insulated copper cables (6491B) enclosed in galvanised steel
                          Controls              cable trunking and heavy duty plastic conduit, XLPE/SWA/LSF
                                                cables and YY PVC/LSF cables fixed to cable tray
                          Fire Alarms           Pirelli FP200 gold fire resistant cable
                          External Lighting and PVC insulated copper cables enclosed in galvanised steel cable
                          Signs                 trunking and heavy duty PVC conduit and PVC/SWA/PVC cables
                          Till Wiring           3 core FP200 cable fixed to cable tray, fabric of the building and
                                                enclosed in flush PVC conduit in walls. STD 13amp FCU with IEC
                                                leads will be used with 5amp fuses


               2.8.2  Armoured Cables


               2.8.2.1  Materials

                                                                              2
                                                    2
                         Armoured cables from 1.5mm up to and including 10mm CSA. shall be XLPE/SWA type.
                                      2
                         Cables 16mm   and above shall be XLPE/SWA type, 600/1000 volt grade PVC  insulated
                         extruded PVC bedded, armoured, LSF  sheathed cables shall conform to  BS 6346 1997

                                                      McDonalds Restaurants Ltd