Page 30 - WM E-Learning Handbook
P. 30
Slide Topic Content Notes
Employee Safety in Vehicle
Maintenance Facilities Two options in the event of a
leak
Employee Safety in Vehicle Continuous ventilation
Maintenance Facilities Methane gas detection
systems
Both meet code
requirements and provide
maximum protection for
employees.
Introduces large amounts of
fresh air into facility
Prevents collection of
combustible mixture of gas in
the event of leak
Facilities use an alarm when
exhaust fans fail or fault or if
fans are manually turned off.
Methane Gas Detection System Activates at 25% LFL and may
in Vehicle Maintenance Facilities perform some or all of the
following
Activates an exterior red
light
Activates internal
audible/visual alarms
Activates emergency
exhaust fans
Activates and opens
make-up air (roll-up
doors, etc.)
Deactivates heating
system
Deactivates welding
receptacles
Notifies your
organization’s security
department
Notifies fire department,
if required
Technician Safety and Awareness Training for NGVs © 2018 NGVi All Rights Reserved Page 28