From  the  evaluation  table,  we  narrowed  the  environmental  review  to  focus  on  several  key  aspects.  Based  on
            this selection, we then started to collect data on the number of air-conditioning units and their settings at the
            company. We estimated power consumption either by using the readings from the energy meter or deriving relevant
            information from the specification of the compressor unit. We also collected data on the number of hours the air-
            conditioning units were operating. Data on air-conditioning use and power consumption is shown in Table 3.



                 Production Floor (Level 1)  Units     Operating Temperature  Power Consumption   Operating Hours
                                                               o
             Window air-conditioning unit      5             16  C               1.1 kW              11 h / day
                                                                  o
                                                             o
             Room air-conditioning unit        3           16  C – 22  C         1.65 kW             9 h / day
                                                               o
             Portable air-conditioning unit    1             20  C              1.195 kW             12 h / day
             Indoor air-conditioning unit      2             16  C               0.85 kW             11 h / day
                                                               o
                     Office (Level 2)
             Room air-conditioning unit        9           16  C – 22  C         1.65 kW             9 h / day
                                                             o
                                                                  o
             Portable air-conditioning unit    1             20  C              1.195 kW             12 h / day
                                                               o
                              Table 3: Air Conditioning usage, operating hours and typical power consumption




            From the information in Table 3, we calculated the annual power consumption to be 71,520 kWh.  Details are given
            in Table 4.


                     Air-conditioning Unit            Power Consumption / day          Annual power Consumption
                                                                                  (based on 250 working days per annum)
             Window air-conditioning unit (5 units)         60.5 kWh                         15,125 kWh
             Room air-conditioning unit (12 units)         178.2 kWh                         44,550 kWh
             Portable air-conditioning unit (2 units)      28.68 kWh                         7,170 kWh

             Indoor air-conditioning unit (2 units)         18.7 kWh                         4,675 kWh
             Total:                                        286.08 kWh                        71,520 kWh

                                        Table 4: Total Power consumption from air conditioning