Output device troubleshooting guide
                                        Output device   Output module  Monitor display
                                          condition    status indicator   status indicator    Fault(s)
                                                                         True
                                                            ON                        None - correct indication
                                        Energized — ON

                                                                         False
                                                           OFF                        None - correct indication
                                      De-energized — OFF

                                                                         True     Output instruction and status indicator
                                                            ON                    agree but the field device does not.
                                      De-energized — OFF                          Open field device or wiring.
                                                                                  Module circuit or fuse.
                                                                         True     Field device status and status indicator
                                                           OFF                    agree but the output condition does not.
                                      De-energized — OFF                          Module circuit or fuse.



                                  Output module
                                  status indicator  Output module
                                      ON                           L1


                                                                           Open in wiring
                                                        VAC
                                                       OUT 0
                                                       OUT 1
                                                       OUT 2
                                                                                                Open in field device
                                                       OUT 3
                                                       OUT 4
                                                       OUT 5
                                                       OUT 6
                                                       OUT 7
                                                      AC COM                                   L2


                               Figure 13-23  Output troubleshooting guide.
                                 Source: Photo courtesy Guardian Electric, www.guardian-electric.com.



                       –  Errors
                               Program Files
                          –
                                      File 2
                            –
                                            Ring 1 Ins 3: ERROR: Unconfigured I/O (I:20/6)
                              Verify Results
                   Figure 13-24  Sample of verifying program errors.


                     Certain diagnostic instructions may be included as part
                   of a PLC’s instruction set for troubleshooting purposes.
                   The  temporary end (TND) instruction, shown in Fig-
                   ure 13-26, is used when you want to change the amount of   Figure 13-25  Indication of enabled forces.
                   logic scanned to progressively debug your program. The   Source: Courtesy of TheLearningPit.



                                                          PLC Installation Practices, Editing, and Troubleshooting  Chapter 13  295