Page 317 - Programmable Logic Controllers, Fifth Edition - Mobile version
P. 317

Output module
                                                                                   Yes
                       Output                                       Turn OFF  Output device  Turn ON
                    0  4  8  12                                               would not
                    1  5  9  13
                    2  6  10 14
                    3  7  11  15
                                                            L1   Output  OFF  Check I/O  ON   Output
                                                                 status      device wiring     status
                                   VAC                          indicators                   indicators
                                         Out 0
                                   Out 1                            ON                           OFF
                                         Out 2  O:2/3
                                  Out 3                R                                     Blown fuse ON  Find out why
                                         Out 4                                                             •  Repair
                                  Out 5                                                       indicator    •  Replace
                                         Out 6
                                  Out 7         O:2/8       L2                                   OFF
                                         Out 8         G
                                  Out 9                          Display                      Display
                                         Out 10
                                  Out 11                         rung on                      rung on
                                         Out 12                  screen                       screen
                                  Out 13
                                         Out 14
                                  Out 15
                                          AC                    Is output    Check I/O        Is output
                                         COM                             No              Yes
                                                                instruction  •  Modules      instruction
                                                                  true?      •  Swing arm      true?
                                                                             •  Power
                                                                    Yes      •  Rack              No


                   Figure 13-30  Troubleshooting tree for a discrete output module.


                If Your Input       And Your Input
                Circuit LED Is . . .  Device Is . . .   And                    Probable Cause

                                    On/Closed/Activated  Your input device will not   Device is shorted or damaged.
                        ON                              turn off.
                                                        Your program operates   Input circuit wiring or module.
                       Input
                                                        as though it is off.   Input is forced off in program.
                    0  4  8  12
                    1  5  9  13     Off/Open/Deactivated  Your program operates   Input device off-state leakage current exceeds
                    2  6  10 14                         as though it is on and/or   input circuit specification.
                    3  7  11  15                        the input circuit will not   Input device is shorted or damaged.
                                                        turn off.
                                                                               Input circuit wiring or module.
                                    On/Closed/Activated  Your program operates   Input circuit is incompatible.
                       OFF                              as though it is off and/or   Low voltage across the input.
                                                        the input circuit will not   Input circuit wiring or module.
                       Input                            turn on.
                                                                               Input signal turn-on time too fast for input circuit.
                    0  4  8  12
                    1  5  9  13     Off/Open/Deactivated  Your input device will not
                    2  6  10 14                         turn on.               Input device is shorted or damaged.
                    3  7  11  15                                               Input is forced on in program.
                                                        Your program operates
                                                        as though it is on.    Input circuit wiring or module.

               Figure 13-31  Input troubleshooting guide.



               298        Chapter 13  PLC Installation Practices, Editing, and Troubleshooting