Page 331 - Programmable Logic Controllers, Fifth Edition - Mobile version
P. 331

Variable (PV), while the desired temperature is
                                    100% - 200 W                       •  The current temperature is called the Process
                                                                          known as the Set-Point (SP).
                                                                       •  The proportional controller changes the controller
                                     50% - 100 W
                                                                          output in proportion to the difference between the
                                                                          SP and PV. The greater the difference, the greater
                                                                          the corrective action applied.
                                     25% - 50 W
                                                                       •  At the set-point (the midpoint of the proportional
                                                                          band), the output on:off ratio is 1:1; that is, the on
                        200 W
                        230 V        12.5% - 25 W                         time and off time are equal.
                                                                       •  If the temperature is further from the set-point, the
                                                                          on and off times vary in proportion to the tempera-
               Figure 14-15  Time proportioning of a heater element.
                                                                          ture difference.
                                                                       •  If the temperature is below the set-point, the output
                  Proportioning action can also be accomplished by        will be on longer; if the temperature is too high, the
               turning  the  final  control  element  on  and  off  for  short   output will be off longer.
               intervals. This time proportioning (also known as pulse
               width modulation) varies the ratio of on time to off.    In theory, a proportional controller should be all that is
               Figure  14-15  shows  an  example  of  time  proportioning   needed for process control. Any change in system output
               used to produce varying wattage from a 200 watt heater   is corrected by an appropriate change in controller output.
               element as follows:                                   Unfortunately, the operation of a proportional controller
                                                                     leads to a steady-state error known as offset, or droop.
                 •  To produce 100 W the heater must be on 50% of    This steady-state error is the difference between the
                    the time.                                        attained value of the controller and the required value that
                 •  To produce 50 W the heater must be on 25% of     results in an offset signal that is slightly lower than the
                    the time.                                        set-point value, as illustrated in Figure 14-17. Depending
                 •  To produce 25 W the heater must be on 12.5% of   on the PLC application, this offset may or may not be
                    the time.                                        acceptable.
                                                                        Proportional control is often used in conjunction with
                  Proportioning action occurs within a proportional band   integral control and/or derivative control.
               around the set-point. The table of Figure 14-16 is an example
               of the proportional band for a heating application with a set-  •  The integral action, sometimes termed reset action,
               point of 500°F and a proportional band of 80°F (±40°F).    responds to the size and time duration of the error
               Proportioning action can be summarized as follows:         signal. An error signal exists when there is a dif-
                 •  Proportional controllers have analog input and out-   ference between the process variable and the set-
                    put values that vary over the range necessary for     point, so the integral action will cause the output
                    control of the process.                               to change and continue to change until the error no
                                                                          longer exists. Integral action eliminates steady-state
                                                                          error. The amount of integral action is measured as
                                                        4–20 mA           minutes per repeat or repeats per minute, which is
                           Time proportional
                                                       proportional       the relationship between changes and time.
                       Percent On time  O	 time  Temp.  Output  Percent
                         on   (seconds) (seconds)  (°F)  level  output
                          0.0   0.0    20.0  over 540  4 mA   0.0
                          0.0   0.0    20.0   540.0   4 mA    0.0
                         12.5   2.5    17.5   530.0   6 mA   12.5
                         25.0   5.0    15.0   520.0   8 mA   25.0      Set-point                             O set signal
                         37.5    7.5   12.5   510.0  10 mA   37.5
                5 0 0    50.0   10.0   10.0   500.0  12 mA   50.0
                         62.5   12.5    7.5   490.0   14 mA  62.5
                         75.0   15.0    5.0   480.0  16 mA   75.0
                         87.5   17.5    2.5   470.0  18 mA   87.5
                        100.0  20.0     0.0   460.0  20 mA  100.0
                        100.0  20.0     0.0  under 460  20 mA  100.0                               Time
               Figure 14-16  Proportional band for a heating application.  Figure 14-17  Proportional control steady-state error.



               312        Chapter 14  Process Control, Network Systems, and SCADA







          pet73842_ch14_305-332.indd   312                                                                              05/11/15   4:27 PM
   326   327   328   329   330   331   332   333   334   335   336