Page 26 - GuardII+ Series 4208 Platform PD User Manual
P. 26

PD Card Operation




                                     NOTE:
                                     Up-Trend  Triggers  will  not  occur  specify  an  operating  point  unless  the
                                     monitor can acquire the machine’s active power and asset temperature
                                     Operating Conditions either through a Remote I/O Unit or directly through
                                     Modbus.  This configuration is done using IAM; refer to Section 6.3.
                                     Similarly,  the  ambient  variation  flag  cannot  occur  unless  the  ambient
                                     conditions are available to the monitor.


              4.6.7.  Load Dependence Triggers

                        These Triggers detect a correlation between increased positive PD levels and increased
                     load  and  resolve  down  to  a  combination  of  input  pair  and  sensor.   This  means  that  load
                     dependence detected on input Phase A Machine PD causes a different Trigger than  load
                     dependence detected on input Phase A System PD; each combination of input and sensor
                     has its own Trigger.
                        The Trigger interval for is 30 days; additionally, the current PD levels must be higher than
                     the  Moderate  Threshold  setting,  and  the  Trigger  must  be  confirmed  over  multiple
                     measurement cycles before the Trigger actually occurs.

                        A measurement saved in the Archive due to a Load Dependence Trigger will appear in
                     PDView with a flag indicating which sensor caused the Trigger:

                        •  An “LD_C1” flag indicates that the load dependence was detected on the ‘C1’ sensor
                        •  An “LD_C2” flag indicates that the load dependence was detected on the ‘C2’ sensor
















                                 Figure 4-6 Example of a Load Dependence Trigger in PDView

                                     NOTE:
                                     Load Dependence Triggers will not occur unless the monitor can acquire
                                     the machine’s active power and asset temperature Operating Conditions
                                     either  through  a  Remote  I/O  Unit  or  directly  through  Modbus.    This
                                     configuration is done using IAM; refer to Section 6.3.











                                                              18
                                                                                          www.irispower.com
   21   22   23   24   25   26   27   28   29   30   31