Page 74 - 14th @ Irving Basis of Design (internal)
P. 74

14th @ IRVING


   64  12  19  15  LEED CS 2009 Scorecard  6/8/2018                        Project Manager: Keith Amann   Built Ecology
                 Certified: 40-49 points; Silver: 50-59 points; Gold: 60-79 points; Platinum: 80 - 110 points  email: keith.amann@wsp.com
   Y   H  L  N                                                        TENANT
                      CREDIT NAME   PTS      LEED CREDIT REQUIREMENTS  SCOPE ITEM  ACTION ITEMS / NOTES  STATUS  TEAM LEAD
                                       M&V plan that evaluates building/system
                                                                                                                RAL
          3     EAc5.1: Measurement & Verification   3  performance according to IPMVP Option D or B.  M&V plan for base building would be required, WSP   WSP
                (C) - Base Building
                                                                           to review with plans for building operation with RAL
                                       Include central metering network to accommodate
                                                                                                                RAL
    3           EAc5.2: Measurement & Verification   3  future submetering; provide process for corrective   Y  Submetering planned  WSP
                (C) - Tenant Submetering
                                       action if targets not met.
                                       Two years of certified green power for 35% of
                                       electricity use (not cost). Defined as electricity usage   Assume will be pursued if needed. Quote based on
    2           EAc6: Green Power ( C )  2  of the C&S square footage, as defined by BOMA, but   Y  estimated electric consumption per SF=~$2,000.  WSP
                                       not less than 15% of building total gross sf.
    4  1  2  6 Materials and Resources (MR)
                                       Recycling collection and storage area(s) for
   P            MRp1: Storage & Collection of   convenient occupant recycling of paper, cardboard,   Confirm location for collection and storage of waste  DBB
                                       glass, plastics, and metals for entire building.
                Recyclables (D)
                                       Maintain 25% (1 pt), 33% (2 pts), 42% (3 pts), 50%
             5  MRc1: Building Reuse - Maintain   5  (4 pts), 75% (5 pts) of existing building structure   N/A
                                       based on surface area (floor and roof decking),
                Existing Walls, Floors & Roof (C)
                                       envelope (skin and framing, excluding windows).
                                       Excludes hazmats
                                       Recycle/divert 50% (1 pt) or 75% (2 pts) of demo and
    2           MRc2: Construction Waste   2  construction waste through on-site separation or co-  Include in specifications. Best practice in NYC  Suffolk
                Management (C)         mingling program
                                       Use salvaged/reused materials for 5% of total
             1  MRc3: Material Reuse (C)  1  materials cost, excluding MEP.
                                       Use materials such that postconsumer recycled
                                       content + 1/2 preconsumer recycled content = 10%   Include in specifications. Target high cost materials   DBB
    1     1     MRc4: Recycled Content (C)  2  (1 pt) or 20% (2 pts) of total materials cost. Excludes   including concrete, steel, curtainwall, gypsum, etc.   Suffolk
                                       MEP.
                                       Specify products extracted, harvested, recovered
                                                                                                                DBB
    1     1     MRc5: Regional Materials (C)  2  AND manufactured within 500 miles of the site for   Include in specifications. Target high cost materials   Suffolk
                                                                           including concrete, steel, curtainwall, gypsum, etc.
                                       10% (1 pt) or 20% (2 pts) of total materials cost.
                                       Excludes MEP.
                                       50% (cost-based) of all new wood based products
       1        MRc6: Certified Wood (C)  1  (including framing, flooring, doors, etc.) to be FSC               DBB
                                       certified.                                                              Suffolk
    8  0  4  0 Indoor Environmental Quality (IEQ)
                                       Meet ASHRAE 62.1-2007 through ventilation rate
   P            IEQp1: Minimum IAQ Performance    procedure for ventilation systems.  Y                         WSP
                (D)
                                       No smoking in building - Exterior smoking areas to
                                                                                                                RAL
   P            IEQp2: Environmental Tobacco   be min. 25 ft. away from entries, outdoor air intakes   Y        WSP
                Smoke (ETS) Control  (D)
                                       and operable windows, with signage.
                                       Install permanent monitoring system that signals
                                       when airflow or CO2 vary by 10% or > from setpoint.    Confirm design intent. This requirement is more
                                                                                                                RAL
          1     IEQc1: Outdoor Air Delivery   1  Monitor CO2 concentrations within all densely   Y  stringent than NYCECC. Must provide air stations on   WSP
                                       occupied spaces. For non-densely occupied spaces,
                                                                           the OA units and a tenant lease requirement to
                Monitoring (D)
                                       provide direct outdoor airflow measurement device to   install within their spaces.
                                       measure the min. outdoor airflow rate.
                                       Mechanically Vent. Spaces: Increase breathing zone
                                       outdoor air ventilation rates by min 30% above
                                       ASHRAE Standard 62.1-2007 in all occupied spaces.   Exploring options for improving air quality with
          1     IEQc2: Increased Ventilation (D)  1  OR                Y   minimal energy penalty. WSP to provide calcs to   WSP
                                       Naturally Vent. Spaces: Prove effective natural
                                       ventilation through CIBSE Applications Manual   determine feasibility based on current design.
                                       10:2005, OR macroscopic analysis required by
                                       ASHRAE 62.1-2007.
                                       IAQ management plan that meets SMACNA, protect
                IEQc3: Construction IAQ   absorptive construction materials and (if air handler
    1           Management Plan: During   1  is used during construction) incorporate MERV 8   Y  Include in specifications and Suffolk to provide draft   Suffolk
                Construction (C)       filters during construction + prior to occupancy.  Plan
                                                                                                                DBB
    1           IEQc4.1: Low-Emitting Materials -   1  All adhesives and sealants within weather barrier to   Y  Include in specifications, Suffolk to track during CA  Suffolk
                                       be low VOC
                Adhesives & Sealants (C)
    1           IEQc4.2: Low-Emitting Materials -   1  All paints and coatings within weather barrier to be   Y  Include in specifications, Suffolk to track during CA  DBB
                                       low VOC
                Paints & Coatings (C)                                                                          Suffolk
                                       Carpet and cushion to be CRI certified, carpet
                                       adhesives to meet IEQc4.1, hard flooring to meet
    1           IEQc4.3: Low-Emitting Materials -   1  FloorScore standard, floor finishes (stain, sealant)   Y  Include in specifications, Suffolk to track during CA  DBB
                Flooring Systems (C)   and tile setting (adhesives, grout) to meet South                       Suffolk
                                       Coast Air Quality standard.
                                       No added urea-formaldehyde in all composite wood
                                                                                                                DBB
    1           IEQc4.4: Low-Emitting Materials,   1  and agrifiber products (including plywood,   Y  Include in specifications, Suffolk to track during CA  Suffolk
                                       particleboard, MDF, etc.) and no added urea-
                Composite Wood & Agrifiber (C)
                                       formaldehyde laminating adhesives used onsite or
                                       shop-applied.
  WSP Built Ecology                                                                                              3 of 4