Page 122 - E:\CloudStation\Project\1 DONE\Ranhill CIMAH\Flip Book\
P. 122

Control of Industrial Major Accident Hazards (CIMAH) Report   Page       15
                                               Ranhill SAJ Sdn. Bhd.                    Revision      01
                                        Part B: Information on the Installation         Date        Aug 2019


               pressure, equivalent to its vapor pressure at the temperature of the contents inside
               the container. For instance, at a temperature of 30°C, the pressure of the chlorine
               inside the container is about 6.0 bar.

               B.3.2 Chlorination Process

               Kampung Tengah 1 Water Treatment Plant

               Liquid chlorine is withdrawn from the containers, vaporized to gas, reduced to  a
               vacuum  in the vacuum regulator, metered and controlled in the chlorinator, mixed
               with service water in the ejector and fed into the process as a solution.





























                                          Figure B.3.2a: KT1 WTP Chlorine Bank

               Chlorine cylinders are arranged in two (2) rows of three (3) cylinders each. Each row
               consists of three (3)  cylinders  which is individually connected  to  a manifold using
               flexible copper tubing and manual isolating valve at the manifold. Chlorine gas is
               withdrawn from  one  row  while the other  row  is on standby mode.  The liquid
               withdrawal is controlled by a manual changeover system, valves and pressure switch
               control. The controller is designed to allow only one-line bank to be open at a time.
               When the line bank is empty a decreasing pressure initiates pressure switch which
               will trigger the alarm. The switching over pressure is set at 1 bar.

               Chlorine gas is fed to the Pre-Chlorination and the Post Chlorination (Disinfection)
               Chlorinator systems. Each system has two (2) vacuum regulators; one (1) duty and
               one (1) standby. The vacuum regulators convert the chlorine pressure to a vacuum.
   117   118   119   120   121   122   123   124   125   126   127