Control of Industrial Major Accident Hazards (CIMAH) Report   Page       18
                                               Ranhill SAJ Sdn. Bhd.                    Revision      01
                                        Part B: Information on the Installation         Date        Aug 2019












































                                          Figure B.3.3a: Storage of the Cylinders

               Kampung Tengah 2 Water Treatment Plant

               Sufficient storage is provided for eight (8) drums of Chlorine. Chlorines are stored
               under a pressure of eight (8) bar and a temperature of 32°C. The storage areas are
               fully enclosed to contain Chlorine leaks and to force ventilation. When ventilated fans
               are operated, a slight negative pressure is maintained in the store and thus prevents
               the  gas from flowing through the clearances of the door and building. Designated
               area is provided for empty and full drums. Chlorine drums are placed on specially
               constructed concrete cradles for standby. The drums are lifted using overhead crane
               for removal back to the chlorine suppliers using lorries. Drum  specification and
               drawing are provided in Appendix B2.