Page 84 - B8773-AEW-XX-XX-PP-A-0001_[P1]_Contractors Manual
P. 84
4.6.2 Extract System Standard canopy dimensions are 2.5m (D) x
2.0m (W) x 0.55m (H) and constructed in welded
The appropriately sized extract canopy located Stainless Steel.
above the oven installed should be connected
to a range of ductwork and be complete with The hood should incorporate a gutter around all
an axial flow extract fan (or other suitable fan edges with a plugged drain connection at the
type) discharging to a convenient location at lowest point. Removable grease catch pans
high level outside the building. are not required. The canopy must be complete
with at least 4No. removable mesh type grease
The minimum canopy footprint must be 2000 x filters. Baffle filters are very efficient at grease
2500mm and to comply with DW172 (for any of removal but offer a far higher air resistance than
the ovens which we currently install). the mesh type. Domino’s bake-off operation
produces very little grease and the extract
As a minimum, the noise level outside the system is predominantly removing heat and gas
building shall not exceed NR40 at a distance combustion fumes. Mesh filters are much more
of 3m from the discharge point. If required, any efficient at removing any fine flour particles
sound attenuators used should be suitable for which may be caught in the airflow. The filters
use in a hot, catering extract environment. should be of a size which will allow them to be
cleaned in the sinks available in the kitchen.
Air resistance should be calculated by the The filters should be arranged within housings at
Contractor to suit each installation and the fan both ends, as part of a plenum system which
selected accordingly. The selected fan should provides balanced extract over the length of
have a duty nominally 20% greater than the the oven.
calculated resistance of the system but shall
have a minimum duty of at least 1.5m³/sec (or as It is important with the modern Middleby
otherwise specified by the oven manufacturer). Marshal ovens that the extract does not draw
This is to allow for reduced efficiency as the noticeably from only one end, or one side. The
system ages and any ‘as installed’ variation in traditional filter bank running along the back
the ductwork resistance. edge only, has caused problems in this respect,
so the preferred option, therefore, is a filter
The fan should always be mounted on anti- bank running front to back at both ends of the
vibration mountings and attached to the canopy (not a central double faced filter bank)
fixed ductwork with flexible connections. The and joined via suitable ductwork or plenum.
fans should be mounted in such a manner as to
be accessible for maintenance and removable The main site electrician will be required to supply
in the event of fan failure. simple on/off switches and wire to isolators
adjacent to each fan. The electrical supply to
Under no circumstances may flexible ductwork each oven socket should be independent so
be used on the extract system, other than the that in the event that one circuit breaker trips,
fan connections. power is not lost to both ovens at the same time.
4.6.2 Extract System 3 February 2016