Page 26 - B8773-AEW-XX-XX-PP-A-0001_[P8]_Contractors Manual
P. 26

2.2.2 Back of House Floor Finish
       Vinyl  sheet  safety  floor  (Altro  Impressionist  II  –
       Mineral) everywhere EXCEPT the customer area.


       All areas behind the counter line, except under
       the  coldroom,  must have the  Altro  coved up
       the walls to a nominal height of at least 200mm.
       If floors are out of level then the cove height/
       tiling must be varied so that the Altro upstand
       is NEVER less than 150mm high on the wall. If it
       is less than 50mm then the bottom row of tiles
       will be cracked by impact from dough dolly’s in
       operation, and the main contractor will be held
       liable.


       Vinyl sheet flooring is to be laid out to minimise
       the number of joints and provide the best visual
       appearance.


       Vinyl sheet must not be coved up walls behind
       the cold room.




































       2.2.2                       Back of House Floor Finish                            3 February 2016