       4.6.8 Air Conditioning
       ‘Comfort  cooling’  will  normally  be  provided      Condensate  from  the  indoor  unit  shall  be
       in  the  form  of  a  split  system  ceiling  mounted   run  to a suitable drain position, in concealed
       cassette  unit  to  provide  both  a  cooling  and    pipework.  Refrigeration  pipework  and  wiring
       heating facility. The equipment shall be supplied     shall be neatly clipped to the structure and fixed
       by a recognized reputable manufacturer and            to cable tray as appropriate. Insulation shall be
       the  HVAC  contractor  shall  be  responsible  for    a cellular foam product using CFC-free blowing
       selecting suitable and appropriate equipment          agents, such as by Armaflex. .
       for the purpose.
                                                             Refrigeration  medium  shall  be  R407C  or  other
       The unit shall be sized with regards to the size      approved and suitable gas.
       of the store and the operating conditions to be
       found therein.                                        As an alternative to a split cassette system, an
                                                             appropriately designed ducted system may be
       The system  shall  generally  comprise  an  indoor    installed if the franchisee wishes.
       cassette  unit,  outdoor  wall/floor  mounted
       condensing  unit  and  all  inter-connecting
       refrigerant pipework, insulation and associated
       power and control wiring from an isolator left by
       the electrical subcontractor.

       The indoor  unit shall  be controlled  by a wall
       mounted hard wired matching controller.

       The face plate of a ceiling mounted indoor unit
       in the Bake & Serve or Customer area must be
       sprayed to RAL 7037 to match the grey ceiling
       colour.

       Units in  other  areas and Wall mounted  units
       should however always be left in standard white.

       The outdoor condensing unit will be wall or floor
       mounted, as shown on the project drawings, at
       a position to give access for maintenance.


       The main electrical contractor  shall  run a
       30amp single phase supply to the position of the
       outdoor unit, terminating in a suitable outdoor
       weathered, lockable isolator.



       4.6.8                       Air Conditioning                                      3 February 2016