       4.6.5 Mechanical Extract to Toilets
       The mechanical extract ventilation of internal
       toilets should be controlled by the light switch,
       being  interlinked  with  the  extract  fan  timer  to
       give minimum 15l/s air change with 20 minute
       overrun.  All  fittings  to  have  anti-vibration
       mountings where appropriate.

       Design of mechanical extract to customer and/
       or staff toilets should be considered in relation
       to the Workplace (Health Safety and Welfare)
       Regulations 1992 (2013 Edn) Paragraph 205 of
       these regulations states; ‘Any room containing a
       toilet should be well ventilated, so that offensive
       odours do not linger. Measures should also be
       taken to prevent odours entering other rooms.
       It  should not  be possible for  air from  a room
       containing a toilet to enter a room where food
       is processed, prepared or eaten.’




       4.6.6 Mechanical Extract to Internal Rooms
       All internal rooms  to  be provided with forced
       ventilation, either via external fan and ductwork,
       or by independent local wall mounted fans. To
       comply with Approved Document F (2010 Edn)
       i.e. 10 l/s/person All fittings to have anti-vibration
       mountings where appropriate.























       4.6.5 - 4.6.6               Mechanical Extract to Toilets and Internal Rooms      3 February 2016