Page 715 - Med Plaza and Cancer Center
P. 715
PROPRIETARY AND CONFIDENTIAL DRAFT 28/Feb/03
Configuring the Area Alarm by Using the Front Panel
Chapter 1: Introduction
1. Scroll through the options, by pressing the Increment key or Decrement
key (see figure 1-58 on page 1-118).
Figure 1-58. Area Alarm Module
2. When the code for the option that you need shows on the display, stop
scrolling.
3. View the setting for that option by pressing and holding the Test key.
4. To change the setting, do the following:
a. Press and hold the Test key while scrolling through the available
options with either the Increment key or Decrement key.
b. When the intended setting displays, release the Test key.
NOTE:
If nA displays, that option is not available.
5. You can return to normal operation and save the changes that you have
made at any time.
Page 1 - 118 MedPlus TotalAlert™ Alarm Network Operation and Maintenance Manual (man291ra)