Page 190 - Womens Pavilion
P. 190

“Oil-Less” Scroll Medical Air


            3.0  System Operation



            3.2  Initial Start-up                                Check all voltages supplied to the LifeLine® system
                                                                 to ensure they are the required value and phases
            CAUTION: Complete the prestart-up procedure          needed by the control panel.
            before continuing with the initial start-up
            procedure                                            Open the inlet isolation valve on each compressor.

                                                                 Open the outlet isolation valve on each compressor.
                               WARNING:

             To prevent electrical shock, ensure that            Open the receiver isolation valves.
             ALL electrical power to the system is OFF,
             including the disconnect switches and               Close the receiver bypass valve.
             Automatic-Manual-Off  touch screens on
             the control panel.  The facility’s supply           Close the DP/CO sensor isolation valve.
             circuit breaker should also be locked out.
                                                                 Close the inlet and outlet valves on both dryer/
                                                                 fi lter/regulator assemblies.
            NOTE: DO NOT ADD OIL TO THE COMPRESSOR.
            The design of the  LifeLine® Scroll compressor       Close the outlet isolation valve.
            is totally oil-less. It is not necessary to fi ll  the
            crankcases with oil.                                 Apply power to the system and turn the disconnect
                                                                 switches to “On”.
            Inside the control panel, make sure that all unit
            printed circuit boards are set to the manual         Inside the control cabinet, switch one of the unit
            override “Off ” position.  This is indicated by the   printed circuit boards from the manual override
            middle position “X” on the three-position sliding    “Off ” position to the bottom position, the default
            switch as shown in Figure 3.2.                       “Automatic” mode.  Make sure the Pump Mode on
                                                                 the Unit touchscreens are in the Off  position, see
                                                                 Figure 3.3.






















                                       Manual Override
                                       Switch                    Figure 3.3 Unit Screen - Off  Position
                                       O - On Manual             Check for correct direction of rotation of each
                                       X - Off                   compressor by pressing the “Rotation” button
                                       A - Automatic             on touchscreen display (found in the Service
            Figure 3.2 Unit PCB Override Switch
                                                             3-3                                  4107 9000 69.06
   185   186   187   188   189   190   191   192   193   194   195