“Oil-Less” Scroll Medical Air
4.0 Trouble Shooting
Problem Possible Causes Solution
Low discharge pressure System piping leaks Repair leaks
Defective pressure sensor Replace sensor
Aftercooler drain solenoid stuck Check electrical connections
open
Belts slipping Adjust tension
Intake fi lter clogged Clean or replace
Compressor cycles too often System undersized Contact BeaconMedæs
Faulty pressure sensor Replace sensor
System piping leaks Repair leaks
Check valve or line to receiver is Replace if necessary
leaking or plugged
Both dryers on line Valve off one dryer
Water in air receiver Drain air receiver
Compressor won’t shut off Pressure sensor faulty Adjust or replace
Excessive belt wear Belt tension Adjust tension
Belt alignment Realign compressor & motor sheaves
Abnormal noise Mounting bolts loose Tighten bolts
Belt tension Adjust tensions
NOTE: For air dryer touble shooting, see Appendix A.