Page 247 - Womens Pavilion
P. 247
“Oil-Less” Scroll Medical Air
Appendix D: TotalAlert Embedded Control System
D.4 Password Access • Maintenance - Testing the System Alarms: The
Testing button allows the operator to create
an Alarm or Shutdown condition to test the
complete alarm network. See section D.5 for
additional information.
• Settings - Pressure: Adjust system “Max” and
“Min” operating pressure settings within a
factory-set range of pressures.
• Settings - Horn: An option is available to
reinitiate the horn during an alarm/shutdown
event. The operator can elect to have the horn
reinitiate after a set period of time after the
silencing of the horn.
Figure D.24 Password Screen
• Settings - Language: The operator can select
from the language options available on the
The TotalAlert Embedded control system contains
items that can be changed or adjusted. Before system.
making any changes on the system or unit screens, • Settings - Display Units: The operator can
a password prompt appears. A proper password
must be entered before adjusting the control select preferences for the display of pressure,
system. See Figure D.24. dew point, and other temperatures.
• Settings - Date and Time: Ensure the correct
The password for the Scroll Medical Air System
is “121212”. After entering the password, the date and time for the system, as this impacts
history log reporting.
password remains valid for approximately ten
minutes or until the unit resets itself to the default • Settings - Network Confi guration: Confi gure
display screens. Reentering the password after how the system operates remotely within the
“timing out” allows the user to continue making existing facility network.
system adjustments.
• Settings - General Options: Select method for
D.4.1 Main Screen Password Items
displaying alarms/shutdowns. Operator can
change the timer setting for sleep mode on the
On the 5.7” main screen, several screens allow
adjustments with the proper password. screens.
D.4.2 Unit Screen Password Items
• Maintenance - Resetting a Service Activity: A
service notifi cation activates when a service In the Service section of the Unit screens, the
item is past due. Upon completion of the operator can create alarm or shutdown conditions
past due service activity, reset the service due to test the complete alarm network. See section
counter by pressing the item on the service D.5 for additional information.
screen, selecting update, and entering the
password when prompted.
4107 9000 69.06 D-12